17
2120 Audio System Upgrade,
Continued
Power
Preamplifier
Configuration
Limitations
The 2120 Power Preamplifier programmer card type will be restricted as to the options allowed:
• Flex-35, 25V type only (4100-1312 or 4100-1326 only)
• Class A NAC Adapter not allowed
• Class B NAC Expander not allowed
• Constant Supervision NAC Adapter not allowed
• Unused NACs on a riser amp are not available for general use
The 4100U/4100ES audio system used in the BMUX replacement can be either analog or digital.
Audio Control
Functions
connected to the
Local BT I/O
card
The local BT card was typically used to support the following monitor and control points when
used with audio systems, these points have similar, but not direct functionality on the 4100U/
4100ES.
When these points are encountered in 2120 SMPL programming, they must be re-programmed (or
removed) for compatibility with 4100U/4100ES audio equipment.
Table 4: Local BT I/O points used for audio
Local BT I/O Point
Purpose
4100U/4100ES Equivalent
All Talk Switch
(Monitor Pt)
Activated when all circuits switch
activated.
All Speakers Talk switch
(LED/Switch point).
Osc Stop / Amp Tbl Byp
(Monitor Pt)
Used in programming to bypass
audio troubles during oscillator
stop conditions.
Pseudos P266 & P267
Audio Playing Silence.
All Evacuate
(Monitor Pt)
A manual switch on the audio con-
trol system. Used in programming
to activate all speaker circuits.
All Speakers Evac switch
(LED/Switch point).
Audio System Tbl
(Monitor Pt)
Activated when there is a preamp
or power preamp trouble.
Audio sub-system trouble
monitoring.
Audio System Act.
(Control Pt)
Contact closure to activate audio
subsystem.
Switch in combination with
speaker select switches.
Message Player Reset
(Control Pt)
Resets the message player.
MIC Talk Internal operation
to 2120 audio. No direct
equivalent.