Chapter 2. Installation and System Checkout
2-13
Auxiliary 24 V Wiring
•
All wiring must be 18 AWG (minimum) to 12 AWG
(maximum).
•
Conductors must test free of all grounds and stray volt-
ages before connection to appliances, devices, and
panel.
•
All wiring is supervised and power-limited.
•
Voltage rating (24 VDC special application): 1 V p-p
ripple (maximum)
-
0.5 A maximum available aux 24 V from EPS
-
Additional 0.5 A maximum available from Main
System Board (MSB) AUX 24 V
-
3 A total available from MSB NACs and MSB
AUX 24 V.
-
3 A total available from EPS NACs and EPS AUX
24 V.
•
Compatible with Simplex 4098 Series Peripherals; 2098
Series Relay Modules; all Simplex 4090 Series IDNet
Peripherals; and 4610-9111 / 4606-9101 Annunciators.
•
If wiring is routed outside the building, use of a listed
secondary protector is required. Use Simplex Model
2081-9028 or 2081-9044. A protector must be installed
at each building exit/entrance. Each 2081-9044 adds 6
ohms wiring resistance, and is rated for 200mA. Each
2081-9028 adds .2 ohms wiring resistance, and is rated
for more than 1/2A Aux. 24V capacity.
•
Compatible devices must operate from a range of 19.5
to 28 VDC or greater, and have a total current draw of 1/
2 A or less.
Figure 2-14 Aux 24V Wiring
Technical Manuals Online! - http://www.tech-man.com
Содержание 4006-9101
Страница 1: ...Technical Manuals Online http www tech man com...
Страница 6: ...Technical Manuals Online http www tech man com...
Страница 11: ...Technical Manuals Online http www tech man com...
Страница 12: ...Technical Manuals Online http www tech man com...
Страница 46: ...Technical Manuals Online http www tech man com...
Страница 60: ...Technical Manuals Online http www tech man com...
Страница 72: ...Technical Manuals Online http www tech man com...
Страница 77: ...Technical Manuals Online http www tech man com...
Страница 78: ...Technical Manuals Online http www tech man com...