Chapter 7. Operating
7-4
Manually Activating a NAC/Relay
Follow these steps to manually turn a NAC or Relay on or
off, or set it to automatic operation.
1.
Press <MENU>.
2.
Press <NEXT> until Control/View is shown.
3.
Press <ENTER>. Use the <NEXT> or <PREV> key to
select NAC or Relay.
4.
Press <ENTER>. Use the <NEXT> or <PREV> key to
scroll through the list of points for NAC or Relay.
5.
Press <ENTER> when the point you want to turn on or
off is displayed.
6.
Press <NEXT> until a prompt similar to the following is
shown.
ENTER = Control AUX
TROUBLE
STEADY
7.
Press <ENTER>. The following prompt appears.
ENTER = Accept
FN: ON
8.
Use <NEXT> to select one of the following:
•
ON. Use this option to turn the relay or NAC on. To
return the NAC/Relay to automatic operation, first
set it to OFF, and then reselect the point and set it to
AUTO.
•
OFF. Turns the relay or NAC off.
•
AUTO. Use this option to return the NAC or Relay
to automatic operation.
Enabling or Disabling Points
Use the following steps to enable or disable points.
1.
Press <MENU>.
2.
Press <NEXT> until Control/View is shown.
3.
Press <ENTER>. Use the <NEXT> or <PREV> key to
select IDC, NAC, or Relay.
4.
Press <ENTER>. Use the <NEXT> or <PREV> key to
scroll through the list of points.
5.
Press <DISABLE/ENABLE> when the point you want
to turn enable/disable is displayed. A prompt similar to
the following appears.
IDC1
FN: [Enable]
6.
Use NEXT to toggle between Enable and Disable. Press
<ENTER>. A prompt appears asking you to confirm the
operation. Press <ENTER>. Keep the following in mind
when enabling/disabling points.
•
When a monitor point is disabled, any status
changes occurring on the point are ignored by the
panel. If a control point is disabled, any automatic
functions are inhibited. A disable trouble will exist
for each disabled point in the system.
•
When a monitor point is enabled, a 30-second
countdown will start to prevent an operator from
accidentally enabling a point that will alarm the
system. The point may be enabled immediately by
pressing <ENTER>, or the enable can be aborted
by pressing <EXIT>.
Control Functions
The panel includes the pre-programmed functions listed in
the table below. To access these functions, press the
<FUNCTION> key, and then use the <NEXT> key to scroll
through the options. Press <ENTER> to activate a function.
The table below shows the operations available in the Func-
tion menu.
Output
(LED)
a.
Press <ENTER> to view a description of
the first system point in the list. Press
NEXT to scroll through the list of points.
System
Point
a.
Press <ENTER> to view a description of
the first system point in the list. Press
NEXT to scroll through the list of points.
Table 7-2 Additional Point Information (Continued)
Table 7-3 Control Functions
Drill
Activates the drill operation (all notifica-
tion appliances).
Manual Evacu-
ation
Activates manual evacuation (general
alarm).
City/DACT
Disconnect
Disconnects the city circuit or DACT
(causes a trouble).
Technical Manuals Online! - http://www.tech-man.com
Содержание 4006-9101
Страница 1: ...Technical Manuals Online http www tech man com...
Страница 6: ...Technical Manuals Online http www tech man com...
Страница 11: ...Technical Manuals Online http www tech man com...
Страница 12: ...Technical Manuals Online http www tech man com...
Страница 46: ...Technical Manuals Online http www tech man com...
Страница 60: ...Technical Manuals Online http www tech man com...
Страница 72: ...Technical Manuals Online http www tech man com...
Страница 77: ...Technical Manuals Online http www tech man com...
Страница 78: ...Technical Manuals Online http www tech man com...