Chapter 3. Programming IDCs, NACs, and AUX Relays
3-2
Keep the following in mind if you are adding or deleting an
expansion IDC module.
•
Adding Expansion IDCs
(only if 4006-9802 Expan-
sion IDC Module is installed). To add an expansion IDC
module to the job, set the “Exp IDC” system option,
described in Chapter 6 of this manual, to ON.
•
Deleting Expansion IDCs
(only if 4006-9802 Expan-
sion IDC Module was previously installed and has been
removed). To delete an expansion IDC module from the
job, change the setting of the “Exp IDC” system option
from ON to OFF. The “Exp IDC” option is described in
Chapter 6 of this manual.
If an Expansion Power Supply Module is installed in the
system, you must first set the Expansion Power Supply sys-
tem option to ON before programming NACs. Refer to
Chapter 6 - System Options for information on doing this.
All operations described in this chapter require you to first
login at Access Level 4. See Chapter 1 for information on
doing this.
Note:
The <Exit/Clear> key is used to back out of menus or
displays and return to the top-level menu structure. Where
possible, the <Exit/Clear> key backs out one level at a time.
There are cases, however, that the Exit/Clear key will return
the operator directly to the top-level menu.
Default General Alarm Programming
The panel ships with the following default programming
installed on the panel.
•
All IDCs are configured as general fire alarm monitor
zones.
•
NAC1 and NAC2 are configured for on-til-silence oper-
ation (temporal coding).
Accessing Menus
Use the following steps to gain access to the programming
menu.
1.
Press the <MENU> key. Press <NEXT> or <PREV>
until the [Programming] option is displayed. Press
<ENTER>. The following displays:
FIRE ALARM
SUSPENDED
<ENTER> to Program
<EXIT> to resume
2.
Press <ENTER>. The Programming menu appears.
[Points] is the default selection, which allows you to
make changes to a specific point’s programming.
<ENTER>=Accept
Prg:[Points]
3.
Press <ENTER>. A prompt appears, allowing you to
select the type of point to manually edit. By default,
[IDC] is the first choice.
<ENTER>=Accept
Prg:[IDC]
4.
Use the <NEXT> and <PREV> keys to scroll to the
appropriate choice and then press <ENTER>.
•
IDC
•
NAC
•
RELAY (Use for on-board and expansion relays).
Select the operation you want to perform and see the appro-
priate section in this chapter. (The other options that appear
when you perform Step 4 -- LED, Input, User SW LED --
apply to annunciators. Programming annunciator points is
described in Chapter 5 of this manual.)
Editing IDCs
Editing an IDC allows you to change the following attributes
for each circuit.
•
Function - change the functional characteristics of each
IDC zone (i.e., change the zone from a Fire monitoring
zone to a Supervisory zone).
•
Alarm Group. Assign the IDC to up to three system
alarm groups.
•
Edit/Clear Label. Allows you to assign or clear the 20-
character custom label for the zone.
Setting IDC Function Type
The Function Type determines the way in which the IDC
operates (whether the zone is a fire, trouble, waterflow/
sprinkler zone, etc.).
1.
Follow the steps in “Accessing Menus”. Make sure to
choose IDC as the type of device to program.
<ENTER>=Accept
Prg: [IDC]
2.
Press <ENTER>. A prompt similar to the following
appears.
<ENTER>=Accept
IDC: [Add]
Technical Manuals Online! - http://www.tech-man.com
Содержание 4006-9101
Страница 1: ...Technical Manuals Online http www tech man com...
Страница 6: ...Technical Manuals Online http www tech man com...
Страница 11: ...Technical Manuals Online http www tech man com...
Страница 12: ...Technical Manuals Online http www tech man com...
Страница 46: ...Technical Manuals Online http www tech man com...
Страница 60: ...Technical Manuals Online http www tech man com...
Страница 72: ...Technical Manuals Online http www tech man com...
Страница 77: ...Technical Manuals Online http www tech man com...
Страница 78: ...Technical Manuals Online http www tech man com...