70
ture, see the paragraph “TO SET HEATING
AND SANITARY WATER TEMPERATURE
FROM THE REMOTE CONTROL PANEL”
HOLIDAY
Plant surveillance is active and services
(heating/sanitary water/zone manage-
ment) are deactivated. On expiry of the
count expressed in days (max. 99), “AUTO-
MATIC” mode will take over again with the
selected programme. The environment
antifreeze function is always active, howe-
ver, and will switch on the boiler when the
environment temperature falls below the
level (min).
ALARMS AND DYSFUNCTIONS
The boiler alarm is triggered off by a combination of:
ALARM
ALL 01:
Fumes thermostat intervention
ALL 02:
Water pressure valve intervention
ALL 04:
Sanitary sensor failure
ALL 05:
Heating sensor failure
ALL 06:
Ion block
The possible dysfunctions are indicated as shown below:
No data connection
Low battery
Flat battery
The possible breakdowns are indicated as shown below:
ERR_01
Circuit temperature measurement error
ERR_02
Supply breakdown
PROGRAMMES
“AUTOMATIC”, “COMFORT” and “HOLIDAY” modes are coordinated by the programmes
winter
between-season
weekly, with temperature-time intervals of 0.5 hour. To change from one programme to
another, go to “AUTOMATIC” mode and press the keys
(+)
and
(-)
.
Levels adjustable:
[min]
and
[T1] [T2] [T3]
.
PLEASE NOTE: If the level (min) is given the value OFF, the boiler will not come on, even if
the environment temperature falls below 0 °C. To assign a temperature value to a level, see
paragraph “PROGRAMMING”.
Fig. 6
SET Min Max
Limits
min
OFF / 0 °C
25 °C
< T1
T1
5 °C
30 °C
> min
< T2
T2
5 °C
30 °C
> T1
< T3
T3
5 °C
30 °C
> T2
°C
–––