114
007-4857-002
6: Maintenance and Upgrade Procedures
4.
Install the new power supply with the retention latch at the top of the supply.
5.
Slide the power supply into the chassis until the retention latch engages.
6.
Reconnect the power cord to the power supply.
7.
Reattach the L1 front panel using the information in “Remove and Replace the System
Control Display Panel” on page 110.
Figure 6-4
Replacing an IRU Power Supply
Removing and Replacing IRU Fans (Blowers)
The IRU fans (blowers) are located at the rear of the unit (see Figure 6-5). You will need to access
the rack from the back to remove and replace a fan. The IRU’s system controller issues a warning
message when a fan is not running properly. This means the RPM level of the fan is not within
tolerance. When an IRU fan fails, the following things happen:
1.
The L1 display on the IRU with the failed fan shows a warning message
ATTN: Fan (
number
) warning
2.
The console will show the same warning indicating the rack and IRU position
001c01 L2> Fan (
number
) warning limit reached @ 0 RPM
Содержание SGI Altix 450
Страница 1: ...SGI Altix 450 System User s Guide Document Number 007 4857 002 ...
Страница 4: ......
Страница 14: ......
Страница 16: ......
Страница 125: ...Altix 42U and 20U Rack Features 007 4857 002 103 Figure 5 1 Tall 42U Altix Rack and Front Lock ...
Страница 128: ......
Страница 139: ...Replacing IRU Components 007 4857 002 117 Figure 6 7 Replacing an IRU Fan B A Tighten screw ...
Страница 152: ...130 007 4857 002 6 Maintenance and Upgrade Procedures Figure 6 16 Extracting the Carrier Metal Filler Plate ...
Страница 164: ......
Страница 186: ......