8550-3 Flow Transmitter

‡ SIGNET

Monitor the flow rate of Channel 1 and Channel 2 simultaneously.
This is the permanent view display.

Monitor the delta flow rate (Channel 1 rate - channel 2 rate = Delta Flow)
This is a permanent display.

Tot1: 1234567.8
Tot2: 123456.78>

Perm1: 1234567.8

Gallons

Perm2: 123456.78

Gallons

Loop 1 Output:

12.00 mA

Loop 2 Output:

12.00 mA

Last CAL:

06-30-01

Flow

Flow1:  6.25 GPM
Flow2:  9.75 GPM

ENTER

VIEW menu

During normal operation, ProcessPro displays the VIEW menu.

When editing the CALIBRATE or OPTIONS menus, ProcessPro will return to the VIEW menu if no activity
occurs for 10 minutes.

To select a VIEW display, press the UP or DOWN arrow keys.  The selections will scroll in a continuous loop.

Changing the VIEW display does not interrupt system operations.

No key code is necessary to change display selection.

Output settings cannot be edited from the VIEW menu.

Hysteresis

Time

Low Setpoint

Process

Relay energized

Relay relaxed

Hysteresis

Time

High Setpoint

Process

3.3 Open Collector Output

The Open collector output can be used as a switch that responds
when the flow rate moves above or below a setpoint, or it can be
used to generate a pulse that is relative to the flow volume or to
the flow rate.

Low

Output triggers when the flow rate is less than the setpoint.
The output will relax when the flow rate moves above the setpoint
plus the hysteresis value.

High

Output triggers when the flow rate is greater than the setpoint.
The output will relax when the flow rate drops below the setpoint
plus the hysteresis value.

Frequency

Output is a pulse stream that is based on the input flow sensor
signal.  Set for 1 (input frequency = output frequency).  Set for
even numbers (2, 4, 6, 8, . . . . 254 maximum) to scale output
frequency.

Pulse

Output is a pulse based on the volume of fluid that passes the
sensor.  Set any value from 0.0001 to 99999.

The output may be disabled (Off) if not used.

Monitor channel 1 and channel 2 Resettable Totalizers. Press the RIGHT
ARROW key to reset the totalizer. If Reset is locked, you must enter Key
Code. Lock or Unlock function is in OPTIONS menu.

Monitor channel 1 Permanent Totalizer value.

Monitor channel 2 Permanent Totalizer value.

Monitor the 4-20 mA Loop 1 output.

Monitor the 4-20 mA Loop 2 output.

Monitor date for scheduled maintenance or date of last calibration.
(See description in Calibrate Menu.)

All of the displays below are temporary.  After ten minutes the display will return to the permanent display.

Flow1:

123.4 GPM

Flow2:

567.8 GPM

Delta Flow:

10.5 GPM

View Menu

Display

Description

Содержание 8550-3

Страница 1: ...sor Inputs Range 0 5 to 1500 Hz Sensor power 2 wire 1 5 mA 5 VDC 1 3 or 4 wire 20 mA 5 VDC 1 Optically isolated from current loop Short circuit protected Flow Flow1 6 25 GPM Flow2 9 75 GPM ENTER 3 8550 090 3 WARNING Remove power to unit before wiring input and output connections Follow instructions carefully to avoid personal injury Contents 1 Specifications 2 Installation 3 Electrical Connections...

Страница 2: ...325 Ω max 18 V 600 Ω max 24 V Terminals 11 16 Flow sensor inputs Terminals 7 10 Open collector Outputs Two transistor outputs programmable see CALIBRATE menu as High or Low setpoint with adjustable hysteresis Pulse based on Volume Frequency based on flow rate May be disabled Off if not used Terminals 1 and 2 AUXILIARY power Used only if the flow sensor requires more than 1 5 mA current For Signet ...

Страница 3: ...4 VDC PLC or Recorder Channel 3 4 20 mA in Channel 4 4 20 mA in Transmitter 1 Terminals Transmitter 2 Terminals PLC Terminals Channel 1 4 20 mA Power Supply 12 24 VDC Channel 2 4 20 mA Channel 2 4 20 mA Channel 1 4 20 mA Channel 1 4 20 mA in Channel 2 4 20 mA in Power Supply 12 24 VDC NC NC Terminals Snsr 2 Gnd SHIELD Snsr 2 IN RED Snsr 2 V BLACK Snsr 1 Gnd SHIELD Snsr 1 IN RED Snsr 1 V BLACK 16 1...

Страница 4: ...a pulse that is relative to the flow volume or to the flow rate Low Output triggers when the flow rate is less than the setpoint The output will relax when the flow rate moves above the setpoint plus the hysteresis value High Output triggers when the flow rate is greater than the setpoint The output will relax when the flow rate drops below the setpoint plus the hysteresis value Frequency Output i...

Страница 5: ...UP UP UP DOWN keys in sequence After entering the Key Code the display will show the first item in the selected menu Step 3 Scroll menu with UP or DOWN arrow keys Step 4 Press RIGHT ARROW key to select menu item to be edited The first display element will begin flashing Step 5 Press UP or DOWN keys to edit the flashing element RIGHT ARROW key advances the flashing element Step 6 Press ENTER key to...

Страница 6: ...t source for Open Collector output 1 Flow sensor 1 Flow sensor 2 or Delta Flow Select the mode of operation for Open Collector output 1 Options available are High Low Pulse volumetric or Frequency based on rate The signal may be disabled if not in use In Low or High Mode this Open Collector output will be activated when the Flow rate reaches this value Be sure to modify this setting if you change ...

Страница 7: ...ust be entered to reset the resettable totalizer Adjust the minimum and maximum current output The display value represents the precise current output Adjustment limits 3 80 mA 4 00 mA 5 00 mA 19 00 mA 20 00 mA 21 00 mA Use this setting to match the system output to any external device Active HIGH This setting is used to turn a device pump valve ON at the setpoint Active LOW This setting is used t...

Страница 8: ... 000 047 Flow transmitter Field mount 3 8550 1P 159 000 048 Flow transmitter Panel mount 3 8550 2 159 000 049 Flow transmitter Field mount with relays 3 8550 2P 159 000 050 Flow transmitter Panel mount with relays 3 8550 3 159 000 051 Flow transmitter Field mount with dual input output 3 8550 3P 159 000 052 Flow transmitter Panel mount with dual input output Accessories Mfr Part No Code Descriptio...

Отзывы: