8550-3 Flow Transmitter Instructions

‡ SIGNET

Adjust the LCD contrast for best viewing.  A setting of 1 is lower contrast, 5 is higher.
Select lower contrast if the display is in warmer ambient surroundings.

Set the decimal to the best resolution for your application.  The display will automatically
scale up to this restriction.
Select *****., ****.*, ***.**, **.***   or *.****

Set the totalizer decimal to the best resolution for your application.
Select ********., *******.*, or ******.**

OFF provides the quickest output response to changes in flow.
LOW averaging  = 4 seconds, HIGH averaging = 8 seconds of input signal.
Longer averaging produces more stable display and output response.

Lock Off : No key code required to reset the resettable totalizer.
Lock On : The Key Code must be entered to reset the resettable totalizer.

Adjust the minimum and maximum current output. The display value represents the
precise current output.
Adjustment limits:
•  3.80 mA < 4.00 mA > 5.00 mA
•  19.00 mA < 20.00 mA > 21.00 mA
Use this setting to match the system output to any external device.

Active HIGH: This setting is used to turn a device (pump, valve) ON at the setpoint.
Active LOW:  This setting is used to turn a device OFF at the setpoint.

Press UP or DOWN keys to manually order any output current value from 3.6 mA to
21.00 mA to test current loop output  #1.

Press UP or DOWN keys to manually toggle the state of open collector output #1.

Contrast:

3

>

Flow1 Decimal

*****.

>

Total1 Decimal

******.**

>

Averaging 1:

Off

>

Total Reset:

Lock Off

>

Loop1 Adjust:

          4.00      mA >

Loop1 Adjust:

          20.00     mA >

Output1 Active:

Low

>

Test Loop1:

>

Test Output 1:

>

All functions labeled "1" will repeat for channel 2.

Options Menu

Display

(Factory settings shown)

Description

Содержание 8550-3

Страница 1: ...sor Inputs Range 0 5 to 1500 Hz Sensor power 2 wire 1 5 mA 5 VDC 1 3 or 4 wire 20 mA 5 VDC 1 Optically isolated from current loop Short circuit protected Flow Flow1 6 25 GPM Flow2 9 75 GPM ENTER 3 8550 090 3 WARNING Remove power to unit before wiring input and output connections Follow instructions carefully to avoid personal injury Contents 1 Specifications 2 Installation 3 Electrical Connections...

Страница 2: ...325 Ω max 18 V 600 Ω max 24 V Terminals 11 16 Flow sensor inputs Terminals 7 10 Open collector Outputs Two transistor outputs programmable see CALIBRATE menu as High or Low setpoint with adjustable hysteresis Pulse based on Volume Frequency based on flow rate May be disabled Off if not used Terminals 1 and 2 AUXILIARY power Used only if the flow sensor requires more than 1 5 mA current For Signet ...

Страница 3: ...4 VDC PLC or Recorder Channel 3 4 20 mA in Channel 4 4 20 mA in Transmitter 1 Terminals Transmitter 2 Terminals PLC Terminals Channel 1 4 20 mA Power Supply 12 24 VDC Channel 2 4 20 mA Channel 2 4 20 mA Channel 1 4 20 mA Channel 1 4 20 mA in Channel 2 4 20 mA in Power Supply 12 24 VDC NC NC Terminals Snsr 2 Gnd SHIELD Snsr 2 IN RED Snsr 2 V BLACK Snsr 1 Gnd SHIELD Snsr 1 IN RED Snsr 1 V BLACK 16 1...

Страница 4: ...a pulse that is relative to the flow volume or to the flow rate Low Output triggers when the flow rate is less than the setpoint The output will relax when the flow rate moves above the setpoint plus the hysteresis value High Output triggers when the flow rate is greater than the setpoint The output will relax when the flow rate drops below the setpoint plus the hysteresis value Frequency Output i...

Страница 5: ...UP UP UP DOWN keys in sequence After entering the Key Code the display will show the first item in the selected menu Step 3 Scroll menu with UP or DOWN arrow keys Step 4 Press RIGHT ARROW key to select menu item to be edited The first display element will begin flashing Step 5 Press UP or DOWN keys to edit the flashing element RIGHT ARROW key advances the flashing element Step 6 Press ENTER key to...

Страница 6: ...t source for Open Collector output 1 Flow sensor 1 Flow sensor 2 or Delta Flow Select the mode of operation for Open Collector output 1 Options available are High Low Pulse volumetric or Frequency based on rate The signal may be disabled if not in use In Low or High Mode this Open Collector output will be activated when the Flow rate reaches this value Be sure to modify this setting if you change ...

Страница 7: ...ust be entered to reset the resettable totalizer Adjust the minimum and maximum current output The display value represents the precise current output Adjustment limits 3 80 mA 4 00 mA 5 00 mA 19 00 mA 20 00 mA 21 00 mA Use this setting to match the system output to any external device Active HIGH This setting is used to turn a device pump valve ON at the setpoint Active LOW This setting is used t...

Страница 8: ... 000 047 Flow transmitter Field mount 3 8550 1P 159 000 048 Flow transmitter Panel mount 3 8550 2 159 000 049 Flow transmitter Field mount with relays 3 8550 2P 159 000 050 Flow transmitter Panel mount with relays 3 8550 3 159 000 051 Flow transmitter Field mount with dual input output 3 8550 3P 159 000 052 Flow transmitter Panel mount with dual input output Accessories Mfr Part No Code Descriptio...

Отзывы: