8550-3 Flow Transmitter Instructions

‡ SIGNET

3.1  System Power/Loop Connections

Auxiliary Power Note:

Auxiliary power is used ONLY if the flow sensors require more than 1.5 mA  of current.  This is limited to the following Signet flow sensors:
        •  2000, 2507, 2530, 2535, 2540 only if manufactured prior to Jan 1999, 7002 Vortex
        •  All dual open-collector sensor systems

Stand-alone application, no current loop used

Transmitter

Terminals

Power

Supply

12–24 VDC

Connection to a PLC with built-in power supply

Internal 

PLC Connection

Connection to a PLC/Recorder, separate supply

Example:  Two transmitters connected to PLC/Recorder with separate power supply

+

PLC or Recorder

Loop 2 –

Loop 2 +

System Power Loop 1 –

System Power Loop 1 +

AUX Power –

AUX Power +

6

5

4

3

2

1

Transmitter

Terminals

Loop 2 –

Loop 2 +

System Power Loop 1 –

System Power Loop 1 +

AUX Power –

AUX Power +

6

5

4

3

2

1

6

5

4

3

2

1

Transmitter

Terminals

Loop 2 –

Loop 2 +

System Power Loop 1 –

System Power Loop 1 +

AUX Power –

AUX Power +

Loop 2 –

Loop 2 +

System Power Loop 1 –

System Power Loop 1 +

AUX Power –

AUX Power +

6

5

4

3

2

1

6

5

4

3

2

1

Loop 2 –

Loop 2 +

System Power Loop 1 –

System Power Loop 1 +

AUX Power –

AUX Power +

Power

Supply

12–24 VDC

+

PLC or Recorder

Channel 3
4-20 mA in

Channel 4
4-20 mA in


+

+

Transmitter 1

Terminals

Transmitter 2

Terminals

PLC Terminals 

Channel 1

4-20 mA

+

Power

Supply

12–24 VDC

Channel 2

4-20 mA

+


+

Channel 2

4-20 mA

+

Channel 1

4-20 mA


+

Channel 1
4-20 mA in

Channel 2
4-20 mA in

+

+

Power

Supply

12–24 VDC

+

NC

NC

Terminals

Snsr 2 Gnd

(SHIELD)

Snsr 2 IN

(RED)

Snsr 2 V+

(BLACK)

Snsr 1 Gnd

(SHIELD)

Snsr 1 IN

(RED)

Snsr 1 V+

(BLACK)

16

15

14

13

12

11

No Aux Power

515/3-8510-XX
525
2100
2517
2536/3-8512-XX
2540/2541
7000 Vortex

Aux Power Required

2000
2507
2530
2535
2540 (mfg prior to Jan 1999)
7002 Vortex
dual open-collector sensor 
systems

Maximum cable length is 200 ft. for 515/8510-XX,
525, 2517 and any sinusoidal flow signal.

Maximum cable length is 1000 ft. for 2536/
8512-XX, 2540/2541, vortex, and any open-
collector flow signal.

 200 ft. (61 m)

 200 ft. (61 m)

A

B

8550-3

Flow

Flow1:  6.25 GPM
Flow2:  9.75 GPM

ENTER

3.2 Sensor Input Connections

Wiring Tips:

Do not route sensor cable in conduit containing AC power wiring.
Electrical noise may interfere with sensor signal.

Routing sensor cable in grounded metal conduit will help prevent
electrical noise and mechanical damage.

Seal cable entry points to prevent moisture damage.

Only one wire should be inserted into a terminal. Splice double
wires outside the terminal.

A

B

 1000 ft. (305 m)

 1000 ft. (305 m)

8550-3

Flow

Flow1:  6.25 GPM
Flow2:  9.75 GPM

ENTER

Содержание 8550-3

Страница 1: ...sor Inputs Range 0 5 to 1500 Hz Sensor power 2 wire 1 5 mA 5 VDC 1 3 or 4 wire 20 mA 5 VDC 1 Optically isolated from current loop Short circuit protected Flow Flow1 6 25 GPM Flow2 9 75 GPM ENTER 3 8550 090 3 WARNING Remove power to unit before wiring input and output connections Follow instructions carefully to avoid personal injury Contents 1 Specifications 2 Installation 3 Electrical Connections...

Страница 2: ...325 Ω max 18 V 600 Ω max 24 V Terminals 11 16 Flow sensor inputs Terminals 7 10 Open collector Outputs Two transistor outputs programmable see CALIBRATE menu as High or Low setpoint with adjustable hysteresis Pulse based on Volume Frequency based on flow rate May be disabled Off if not used Terminals 1 and 2 AUXILIARY power Used only if the flow sensor requires more than 1 5 mA current For Signet ...

Страница 3: ...4 VDC PLC or Recorder Channel 3 4 20 mA in Channel 4 4 20 mA in Transmitter 1 Terminals Transmitter 2 Terminals PLC Terminals Channel 1 4 20 mA Power Supply 12 24 VDC Channel 2 4 20 mA Channel 2 4 20 mA Channel 1 4 20 mA Channel 1 4 20 mA in Channel 2 4 20 mA in Power Supply 12 24 VDC NC NC Terminals Snsr 2 Gnd SHIELD Snsr 2 IN RED Snsr 2 V BLACK Snsr 1 Gnd SHIELD Snsr 1 IN RED Snsr 1 V BLACK 16 1...

Страница 4: ...a pulse that is relative to the flow volume or to the flow rate Low Output triggers when the flow rate is less than the setpoint The output will relax when the flow rate moves above the setpoint plus the hysteresis value High Output triggers when the flow rate is greater than the setpoint The output will relax when the flow rate drops below the setpoint plus the hysteresis value Frequency Output i...

Страница 5: ...UP UP UP DOWN keys in sequence After entering the Key Code the display will show the first item in the selected menu Step 3 Scroll menu with UP or DOWN arrow keys Step 4 Press RIGHT ARROW key to select menu item to be edited The first display element will begin flashing Step 5 Press UP or DOWN keys to edit the flashing element RIGHT ARROW key advances the flashing element Step 6 Press ENTER key to...

Страница 6: ...t source for Open Collector output 1 Flow sensor 1 Flow sensor 2 or Delta Flow Select the mode of operation for Open Collector output 1 Options available are High Low Pulse volumetric or Frequency based on rate The signal may be disabled if not in use In Low or High Mode this Open Collector output will be activated when the Flow rate reaches this value Be sure to modify this setting if you change ...

Страница 7: ...ust be entered to reset the resettable totalizer Adjust the minimum and maximum current output The display value represents the precise current output Adjustment limits 3 80 mA 4 00 mA 5 00 mA 19 00 mA 20 00 mA 21 00 mA Use this setting to match the system output to any external device Active HIGH This setting is used to turn a device pump valve ON at the setpoint Active LOW This setting is used t...

Страница 8: ... 000 047 Flow transmitter Field mount 3 8550 1P 159 000 048 Flow transmitter Panel mount 3 8550 2 159 000 049 Flow transmitter Field mount with relays 3 8550 2P 159 000 050 Flow transmitter Panel mount with relays 3 8550 3 159 000 051 Flow transmitter Field mount with dual input output 3 8550 3P 159 000 052 Flow transmitter Panel mount with dual input output Accessories Mfr Part No Code Descriptio...

Отзывы: