background image

page 2 of 8

8550-3 Flow Transmitter

‡ SIGNET

Output 2-

Output 2+

Output 1-

Output 1+

10

9

8

7

Loop 2-

Loop 2+

System Pwr
Loop -

System Pwr
Loop +

AUX
Power -

AUX
Power +

6

5

4

3

2

1

Snsr 2 Gnd
(SHIELD)

Snsr 2 IN
(RED)

Snsr 2 V+
(BLACK)

Snsr 1 Gnd
(SHIELD)

Snsr 1 IN
(RED)

Snsr 1 V+
(BLACK)

16

15

14

13

12

11

3.

Electrical Connections

Caution:

  Failure to fully open terminal jaws before removing wire may permanently damage instrument.

Wiring Procedure

1.

Remove 0.5 - 0.625 in. (13-16 mm) of insulation from wire end.

2.

Press the orange terminal lever downward with a small screwdriver to open terminal jaws.

3.

Insert exposed (non-insulated) wire end in terminal hole until it bottoms out.

4.

Release orange terminal lever to secure wire in place.  Gently pull on each wire to ensure a good connection.

Wiring Removal Procedure

1.

Press the orange terminal lever downward with a small screwdriver to open terminal jaws.

2.

When fully open, remove wire from terminal.

2

1

1

Internal open-collector

output circuit

Outputs

Isolation

15

S

D

2

_

+

Terminals 3-6: Loop Power

12-24 VDC 

±

10% system power and current loop outputs.

Max. loop impedance:

  50 

 max. @ 12 V

325 

 max. @ 18 V

600 

 max. @ 24 V

Terminals 11-16: Flow sensor inputs

Terminals 7-10: Open-collector Outputs

Two transistor outputs, programmable (see CALIBRATE menu) as:

• High or Low setpoint with adjustable hysteresis
• Pulse based on Volume.
• Frequency based on flow rate
• May be disabled (Off) if not used.

Terminals 1 and 2:  AUXILIARY power

Used only if the flow sensor requires more
than 1.5  mA current.  For Signet sensors
this is limited to the following products:
•  2000

•  2507

•  2530

•  2535

•  2540 if mfg. prior to Jan. 1999
•  7002 Vortex sensor
•  Dual open-collector sensors

2.1 Panel Installation

1. The panel mount transmitter is designed for installation using a 1/4 DIN Punch.  For

manual panel cutout, an adhesive template is provided as an installation guide.
Recommended clearance on all sides between instruments is 1 inch.

2. Place gasket on instrument, and install in panel.
3. Slide mounting bracket over back of instrument until quick-clips snap into latches on

side of instrument.

4. To remove, secure instrument temporarily with tape from front or grip from rear of

instrument.  DO NOT RELEASE.

Press quick-clips outward and remove.

quick-clips

gasket

panel

terminals

mounting

bracket

latch

Outp

ut -

Out

put +

Sys

tem

 Pw

r

Loo

p -

Sys

tem

 Pw

r

Loo

p +

2

1

4

3

Sen

sr G

nd

(SH

IELD

)

Sen

sr IN

(RE

D)

Sen

sr V

+

(BLA

CK)

7

6

5

Panel Mount
Installation Detail

Содержание 8550-3

Страница 1: ...sor Inputs Range 0 5 to 1500 Hz Sensor power 2 wire 1 5 mA 5 VDC 1 3 or 4 wire 20 mA 5 VDC 1 Optically isolated from current loop Short circuit protected Flow Flow1 6 25 GPM Flow2 9 75 GPM ENTER 3 8550 090 3 WARNING Remove power to unit before wiring input and output connections Follow instructions carefully to avoid personal injury Contents 1 Specifications 2 Installation 3 Electrical Connections...

Страница 2: ...325 Ω max 18 V 600 Ω max 24 V Terminals 11 16 Flow sensor inputs Terminals 7 10 Open collector Outputs Two transistor outputs programmable see CALIBRATE menu as High or Low setpoint with adjustable hysteresis Pulse based on Volume Frequency based on flow rate May be disabled Off if not used Terminals 1 and 2 AUXILIARY power Used only if the flow sensor requires more than 1 5 mA current For Signet ...

Страница 3: ...4 VDC PLC or Recorder Channel 3 4 20 mA in Channel 4 4 20 mA in Transmitter 1 Terminals Transmitter 2 Terminals PLC Terminals Channel 1 4 20 mA Power Supply 12 24 VDC Channel 2 4 20 mA Channel 2 4 20 mA Channel 1 4 20 mA Channel 1 4 20 mA in Channel 2 4 20 mA in Power Supply 12 24 VDC NC NC Terminals Snsr 2 Gnd SHIELD Snsr 2 IN RED Snsr 2 V BLACK Snsr 1 Gnd SHIELD Snsr 1 IN RED Snsr 1 V BLACK 16 1...

Страница 4: ...a pulse that is relative to the flow volume or to the flow rate Low Output triggers when the flow rate is less than the setpoint The output will relax when the flow rate moves above the setpoint plus the hysteresis value High Output triggers when the flow rate is greater than the setpoint The output will relax when the flow rate drops below the setpoint plus the hysteresis value Frequency Output i...

Страница 5: ...UP UP UP DOWN keys in sequence After entering the Key Code the display will show the first item in the selected menu Step 3 Scroll menu with UP or DOWN arrow keys Step 4 Press RIGHT ARROW key to select menu item to be edited The first display element will begin flashing Step 5 Press UP or DOWN keys to edit the flashing element RIGHT ARROW key advances the flashing element Step 6 Press ENTER key to...

Страница 6: ...t source for Open Collector output 1 Flow sensor 1 Flow sensor 2 or Delta Flow Select the mode of operation for Open Collector output 1 Options available are High Low Pulse volumetric or Frequency based on rate The signal may be disabled if not in use In Low or High Mode this Open Collector output will be activated when the Flow rate reaches this value Be sure to modify this setting if you change ...

Страница 7: ...ust be entered to reset the resettable totalizer Adjust the minimum and maximum current output The display value represents the precise current output Adjustment limits 3 80 mA 4 00 mA 5 00 mA 19 00 mA 20 00 mA 21 00 mA Use this setting to match the system output to any external device Active HIGH This setting is used to turn a device pump valve ON at the setpoint Active LOW This setting is used t...

Страница 8: ... 000 047 Flow transmitter Field mount 3 8550 1P 159 000 048 Flow transmitter Panel mount 3 8550 2 159 000 049 Flow transmitter Field mount with relays 3 8550 2P 159 000 050 Flow transmitter Panel mount with relays 3 8550 3 159 000 051 Flow transmitter Field mount with dual input output 3 8550 3P 159 000 052 Flow transmitter Panel mount with dual input output Accessories Mfr Part No Code Descriptio...

Отзывы: