18
SIVACON S8 Planning Principles –
SIVACON S8 – System overview
2.5 Overview of mounting designs
Circuit-breaker design
Universal mounting design
In-line design, plug-in
Fixed-mounted design
In-line design,
fixed-mounted
Reactive power compensation
Mounting design
Withdrawable design
Fixed mounted design
Withdrawable design
Fixed-mounted design with compartment doors
Plug-in design
Plug-in design
Fixed-mounted design with front covers
Fixed mounted design
Fixed mounted design
Functions
Incoming unit
Outgoing unit
Coupler
Cable feeders
Motor feeders (MCC)
Cable feeders
Cable feeders
Cable feeders
Central compensation of reactive power
Rated current
I
n
Up to 6,300 A
Up to 630 A
Up to 630 A
Up to 630 A
Up to 630 A
Non-choked up to 600 kvar
Choked up to 500 kvar
Connection type
Front and rear side
Front and rear side
Front side
Front side
Front side
Front side
Cubicle width
400, 600, 800, 1,000, 1,400 mm
600, 1,000, 1,200 mm
1,000, 1,200 mm
1,000, 1,200 mm
600, 800, 1,000 mm
800 mm
Internal separation
Form 1, 2b, 3a, 4b, 4 type 7 (BS)
Form 3b, 4a, 4b, 4 type 7 (BS)
Form 3b, 4b
Form 1, 2b, 3b, 4a, 4b
Form 1, 2b
Form 1, 2b
Busbar position
Rear, top
Rear, top
Rear, top
Rear, top
Rear
Rear, top, without
Tab. 2/10:
Basic data of the different mounting designs
Содержание Sivacon S8
Страница 1: ...Totally Integrated Power www siemens com sivacon s8 SIVACON S8 Technical Planning Information 10 2015 ...
Страница 2: ......
Страница 6: ...Chapter 1 System based power distribution ...
Страница 23: ...20 SIVACON S8 Planning Principles SIVACON S8 System overview ...
Страница 35: ...32 SIVACON S8 Planning Principles Circuit breaker design ...
Страница 93: ...90 SIVACON S8 Planning Principles Conforming to standards and design verified ...