38
SIVACON S8 Planning Principles –
Universal mounting design
available for the installation of in-line switch-disconnectors.
The basic cubicle characteristics are stated in Tab. 4/6.
Further information about in-line switch-disconnectors with
fuses can be found in Chapter Chapter 5.
Tab. 4/7:
General cubicle characteristics for the withdrawable design
Application range
- Incoming feeders up to 630 A
- Outgoing cable feeders up to 630 A
- Outgoing motor feeders up to 630 A
Form of internal separation
- Form 3b, 4b
1)
Compartment door,
compartment cover
Design options
- Withdrawable unit in compartment
- Reserve compartment
- Empty compartment, device compartment
Design variants for feeders
2)
- Standard feature design (SFD)
- High feature design (HFD)
1)
Also form 4b type 7 in acc. with BS EN 61439-2 possible
2)
Withdrawable unit variants SFD and HFD can be mixed within one cubicle
Fig. 4/5:
Design variants of the withdrawable units in standard feature design (SFD; left) and high feature design (HFD; right)
4.2 In-line switch-disconnectors
with fuses (3NJ62 / SASIL plus)
For the cubicle in universal mounting design, an adapter is
available that allows the installation of in-line switch-dis-
connectors with fuses. This adapter is mounted at the
bottom of the cubicle. It occupies 600 mm in the cubicle's
device compartment. An installation height of 500 mm is
4.3 Withdrawable design
If fast replacement of functional units is required in order to
prevent downtimes, the withdrawable design offers a safe
and flexible solution. Regardless of whether small or nor-
mal withdrawable units are used, the size is optimally
Tab. 4/6:
Cubicle characteristics for in-line switch-disconnectors
adapted for the required performance. The patented with-
drawable unit contact system has been designed to be
user-friendly and wear-resistant. Tab. 4/7 lists typical cubi-
cle characteristics of the withdrawable design.
Application range
- Incoming feeders up to 630 A
- Outgoing cable feeders up to 630 A
Form of internal separation
- Form 3b, 4b
Degree of protection
- Up to IP41
Ventilated
Cubicle dimensions
- Width (front connection in cubicle)
1,000, 1,200 mm
Содержание Sivacon S8
Страница 1: ...Totally Integrated Power www siemens com sivacon s8 SIVACON S8 Technical Planning Information 10 2015 ...
Страница 2: ......
Страница 6: ...Chapter 1 System based power distribution ...
Страница 23: ...20 SIVACON S8 Planning Principles SIVACON S8 System overview ...
Страница 35: ...32 SIVACON S8 Planning Principles Circuit breaker design ...
Страница 93: ...90 SIVACON S8 Planning Principles Conforming to standards and design verified ...