34
SIVACON S8 Planning Principles –
Universal mounting design
designs makes for a space-optimized structure of the
switchboard. Tab. 4/1 gives an overview of the general
cubicle characteristics.
The universal mounting design of SIVACON S8 switch-
boards (Fig. 4/1) allows outgoing feeders in withdrawable
design, fixed-mounted design and plug-in in-line design to
be implemented. A combination of these mounting
4 Universal mounting design
Tab. 4/1:
General cubicle characteristics for the universal mounting design
Application range
- Incoming feeders up to 630 A
- Outgoing cable feeders up to 630 A
- Outgoing motor feeders up to 630 A
Degrees of protection
- Up to IP43
Ventilated
- IP54
Non-ventilated
Cubicle dimensions
- Cubicle height
2,000, 2,200 mm
- Cubicle width (rear connection in cubicle)
600 mm
- Cubicle width (front connection in cubicle)
1,000, 1,200 mm
Device compartment
- Height
1,600, 1,800 mm
- Width
600 mm
Form of internal separation
- Up to form 4b
1)
Compartment door, functional
compartment door
Mounting designs
- Withdrawable design
- Fixed-mounted design with compartment door
- In-line switch-disconnectors 3NJ62 with fuses
2)
- In-line switch-disconnectors SASIL plus with fuses (Jean Müller)
2)
1)
Dependent on mounting design
2)
Front connection in cubicle
Fig. 4/1:
Cubicles for universal mounting design: on the left with front cable connection; on the right for rear cable connection
Содержание Sivacon S8
Страница 1: ...Totally Integrated Power www siemens com sivacon s8 SIVACON S8 Technical Planning Information 10 2015 ...
Страница 2: ......
Страница 6: ...Chapter 1 System based power distribution ...
Страница 23: ...20 SIVACON S8 Planning Principles SIVACON S8 System overview ...
Страница 35: ...32 SIVACON S8 Planning Principles Circuit breaker design ...
Страница 93: ...90 SIVACON S8 Planning Principles Conforming to standards and design verified ...