47
SIVACON S8 Planning Principles –
Universal mounting design
2
3
4
5
6
7
8
9
10
11
1
Small withdrawable unit
1)
Motor
power
P
(AC-2/AC3)
Minimum withdrawable unit size
at 35 °C ambient temperature
Height 150 mm
Height 200 mm
Direct
contactor
Reversing
circuit
Direct
contactor
Reversing
circuit
0.25 kW
¼, ½
¼, ½
¼, ½
¼, ½
0.37 kW
¼, ½
¼, ½
¼, ½
¼, ½
0.55 kW
¼, ½
¼, ½
¼, ½
¼, ½
0.75 kW
¼, ½
¼, ½
¼, ½
¼, ½
1.1 kW
¼, ½
¼, ½
¼, ½
¼, ½
1.5 kW
¼, ½
¼, ½
¼, ½
¼, ½
2.2 kW
¼, ½
¼, ½
¼, ½
¼, ½
3 kW
¼, ½
¼, ½
¼, ½
¼, ½
4 kW
¼, ½
¼, ½
¼, ½
¼, ½
5.5 kW
¼, ½
¼, ½
¼, ½
¼, ½
7.5 kW
¼, ½
¼, ½
¼, ½
¼, ½
11 kW
½
½
½
½
15 kW
½
½
½
½
18.5 kW
½
-
½
½
22 kW
½
-
½
½
30 kW
-
-
½
-
Tab. 4/19:
Minimum withdrawable unit sizes for:
fused motor feeders, 400 V, CLASS 10,
with SIMOCODE, type 2 at 50 kA
Normal withdrawable unit
Motor
power
P
(AC-2/AC3)
Minimum withdrawable unit height
at 35 °C ambient temperature
Direct
contactor
Reversing
circuit
Star-delta
0.25 kW
100 mm
100 mm
150 mm
0.37 kW
100 mm
100 mm
150 mm
0.55 kW
100 mm
100 mm
150 mm
0.75 kW
100 mm
100 mm
150 mm
1.1 kW
100 mm
100 mm
150 mm
1.5 kW
100 mm
100 mm
150 mm
2.2 kW
100 mm
100 mm
150 mm
3 kW
100 mm
100 mm
150 mm
4 kW
100 mm
100 mm
150 mm
5.5 kW
100 mm
100 mm
150 mm
7.5 kW
100 mm
100 mm
150 mm
11 kW
100 mm
100 mm
150 mm
15 kW
100 mm
100 mm
150 mm
18.5 kW
150 mm
150 mm
200 mm
22 kW
150 mm
150 mm
200 mm
30 kW
150 mm
250 mm
250 mm
37 kW
150 mm
250 mm
250 mm
45 kW
150 mm
250 mm
250 mm
55 kW
300 mm
400 mm
400 mm
75 kW
300 mm
400 mm
400 mm
90 kW
300 mm
400 mm
400 mm
110 kW
400 mm
500 mm
500 mm
132 kW
500 mm
500 mm
700 mm
160 kW
500 mm
500 mm
700 mm
200 kW
700 mm
700 mm
700 mm
250 kW
700 mm
700 mm
700 mm
1)
Type: ¼ = small withdrawable unit size ¼
½ = small withdrawable unit size ½
Small withdrawable unit
1)
Motor
power
P
(AC-2/AC3)
Minimum withdrawable unit size
at 35 °C ambient temperature
Height 150 mm
Height 200 mm
Direct
contactor
Reversing
circuit
Direct
contactor
Reversing
circuit
0.25 kW
½
-
¼, ½
¼, ½
0.37 kW
½
-
¼, ½
¼, ½
0.55 kW
½
-
¼, ½
¼, ½
0.75 kW
½
-
¼, ½
¼, ½
1.1 kW
½
-
¼, ½
¼, ½
1.5 kW
½
-
¼, ½
¼, ½
2.2 kW
½
-
¼, ½
¼, ½
3 kW
½
-
¼, ½
¼, ½
4 kW
½
-
¼, ½
¼, ½
5.5 kW
½
-
¼, ½
¼, ½
7.5 kW
½
-
¼, ½
¼, ½
11 kW
½
-
¼, ½
¼, ½
15 kW
½
-
½
½
18.5 kW
½
-
½
½
Tab. 4/20:
Minimum withdrawable unit sizes for:
fuseless motor feeders, 400 V, CLASS 10,
overload protection with circuit-breaker, type 2 at 50 kA
Normal withdrawable unit
Motor
power
P
(AC-2/AC3)
Minimum withdrawable unit height
at 35 °C ambient temperature
Direct
contactor
Reversing
circuit
Star-delta
0.25 kW
100 mm
100 mm
200 mm
0.37 kW
100 mm
100 mm
200 mm
0.55 kW
100 mm
100 mm
200 mm
0.75 kW
100 mm
100 mm
200 mm
1.1 kW
100 mm
100 mm
200 mm
1.5 kW
100 mm
100 mm
200 mm
2.2 kW
100 mm
100 mm
200 mm
3 kW
100 mm
100 mm
200 mm
4 kW
100 mm
100 mm
200 mm
5.5 kW
100 mm
150 mm
200 mm
7.5 kW
100 mm
150 mm
200 mm
11 kW
100 mm
150 mm
200 mm
15 kW
150 mm
150 mm
200 mm
18.5 kW
150 mm
150 mm
200 mm
22 kW
150 mm
150 mm
200 mm
30 kW
200 mm
200 mm
200 mm
37 kW
200 mm
200 mm
200 mm
45 kW
200 mm
200 mm
200 mm
55 kW
400 mm
500 mm
250 mm
75 kW
400 mm
500 mm
250 mm
90 kW
400 mm
500 mm
500 mm
110 kW
500 mm
600 mm
500 mm
132 kW
500 mm
600 mm
500 mm
160 kW
500 mm
600 mm
500 mm
200 kW
600 mm
700 mm
700 mm
250 kW
600 mm
700 mm
700 mm
1)
Type: ¼ = small withdrawable unit size ¼
½ = small withdrawable unit size ½
Содержание Sivacon S8
Страница 1: ...Totally Integrated Power www siemens com sivacon s8 SIVACON S8 Technical Planning Information 10 2015 ...
Страница 2: ......
Страница 6: ...Chapter 1 System based power distribution ...
Страница 23: ...20 SIVACON S8 Planning Principles SIVACON S8 System overview ...
Страница 35: ...32 SIVACON S8 Planning Principles Circuit breaker design ...
Страница 93: ...90 SIVACON S8 Planning Principles Conforming to standards and design verified ...