background image

Ulusoy HMH24-01

Incoming-Outgoing Switchgear with Load Break Switch

User Manual

www.

eaton

.com

Summary of Contents for Ulusoy HMH24-01

Page 1: ...Ulusoy HMH24 01 Incoming Outgoing Switchgear with Load Break Switch User Manual www eaton com ...

Page 2: ...ALLATION 2 INTRODUCTION OF SWITCHGEAR 3 DIMENSIONS 4 CHECKINGS BEFORE ENERGIZING THE SWITCHGEARS 7 TEST TO BE CARRIED OUT BEFORE ENERGIZING SWITCHGEARS 5 INDOOR INSTALLATION 6 INSTALLATION OF BUSBARS 7 ENERGIZINGTHESWITCHGEAR 11 OPERATINGINSTRUCTIONS 12 INSTALLINGPADLOCK 16 SAFE USE 16 TROUBLESHOOTING 17 ...

Page 3: ...klift Transportation with Sling Transportation on Pipes Roll on the pipes Carry with palette Max 90 Remove the bolts which mounts the switchgear to the palette Ulusoy HMH24 01 Incoming Outgoing Switchgear with LBS User Manual August 2020 www eaton com 1 ...

Page 4: ... which mounts the switchgear to the palette Disassemble the top sheet metal Disassemble the lifting plates Pull out the front door of the switchgear f N Storage Instructions 2 Ulusoy HMH24 01 Incoming Outgoing Switchgear with LBS User Manual August 2020 www eaton com ...

Page 5: ...tchgear with LBS User Manual August 2020 www eaton com 3 24 01ING 0 0 0 I I ulusoy info eaton com ANKARA TEL 90 312 267 07 12 FAX 90 312 267 05 17 www ULUSOY Standard IEC 62271 200 0 I 0 I CLOSE THE SWITCHGEAR S DOOR OPEN THE EARTHING SWITCH ASSEMBLE THE COIL SPRING LOAD BREAK SWITCHGEAR CLOSE LOAD BREAK SWITCHGEAR OPEN IS THERE ANY OPERATION ON THE SWITCHGEAR CLOSE THE EARTHING SWITCH OPEN THE SW...

Page 6: ...ons Internal side view Top view Internal front view Side view Front view 4 Ulusoy HMH24 01 Incoming Outgoing Switchgear with LBS User Manual August 2020 www eaton com 1200 960 1900 1800 240 263 222 222 254 260 ...

Page 7: ... 267 05 17 www ULUSOY Standard IEC 62271 200 0 I 0 I CLOSE THE SWITCHGEAR S DOOR OPEN THE EARTHING SWITCH ASSEMBLE THE COIL SPRING LOAD BREAK SWITCHGEAR CLOSE LOAD BREAK SWITCHGEAR OPEN IS THERE ANY OPERATION ON THE SWITCHGEAR CLOSE THE EARTHING SWITCH OPEN THE SWITCHGEAR S DOOR OPERATIONNAL DIAGRAM YES NO IF THIS SWITCHGEAR IS USED AS AN INCOMING FEEDER DO NOT CLOSE THE EARTING SWITCH BEFORE CUTT...

Page 8: ... Indoor Installation Safety distances Front view Top view Side view Cable Channel Wall Wall 6 Ulusoy HMH24 01 Incoming Outgoing Switchgear with LBS User Manual August 2020 www eaton com Top view Side view Front view Cable channel Cable channel 437 150 437 687 300 600 550 550 200 300 450 550 300 1800 100 100 Wall Wall 100 ...

Page 9: ...usbars Remove the bolts spheres and replace the bars Put the bolts and tighten spheres again torque value to be checked 50Nm Ulusoy HMH24 01 Incoming Outgoing Switchgear with LBS User Manual August 2020 www eaton com 7 ...

Page 10: ...the switchgears Side cover of the switchgears are mounted for the first and the last unit Remove the cable clamps and bottom sheet of the switchgear Then use 4 fixing holes at the bottom of the switchgear After fixing the switchgear on the floor Re install the bottom metal sheet and cable clamps 8 Ulusoy HMH24 01 Incoming Outgoing Switchgear with LBS User Manual August 2020 www eaton com ...

Page 11: ...ection equipment M8x20mm bolts to connect U earthing coppers Connect the earthing cable to the first and the last switchgear s earthing bar Connect the cable to L1 inner phase Torque with 50Nm Put the bottom sheet and close the cable clamps After that apply the same prosedure to L2 and L3 Ulusoy HMH24 01 Incoming Outgoing Switchgear with LBS User Manual August 2020 www eaton com 9 Busbar connectio...

Page 12: ...u can connect the auxiliary supply cable to the first or the last switchgear of the set Follow the wiring scheme of switchgear to know how to connect aux supply circuit Supplying Auxiliary Circuit 10 Ulusoy HMH24 01 Incoming Outgoing Switchgear with LBS User Manual August 2020 www eaton com ...

Page 13: ...ton com ANKARA TEL 90 312 267 07 12 FAX 90 312 267 05 17 www ULUSOY Standard IEC 62271 200 0 I 0 I CLOSE THE SWITCHGEAR S DOOR OPEN THE EARTHING SWITCH ASSEMBLE THE COIL SPRING LOAD BREAK SWITCHGEAR CLOSE LOAD BREAK SWITCHGEAR OPEN IS THERE ANY OPERATION ON THE SWITCHGEAR CLOSE THE EARTHING SWITCH OPEN THE SWITCHGEAR S DOOR OPERATIONNAL DIAGRAM YES NO IF THIS SWITCHGEAR IS USED AS AN INCOMING FEED...

Page 14: ...surements Outgoing Switchgears In order to check cable faults Open LBS De energize the switchgear from the previous center and earth the cables Close earthing switch of the switchgear Open switchgear front door Place cable test device After test close the door Reopen earthing switch Perform required measurements Incoming Switchgears In order to check cable faults Voltage Indicator Operation Instru...

Page 15: ... housing as shown and rotate in arrow direction Position after the earthing switch is opened Earthing switch open closing spring idle LBS open DO NOT INVERVENE THE EARTH MECHANISM WHILE LOAD ISOLATOR SPRING IS INSTALLED REMOVE THE INSTALLATION ARM FROM ITS HOUSING AFTER INSTALLING LOAD ISOLATOR SPRING 0 DO NOT INVERVENE THE EARTH MECHANISM WHILE LOAD ISOLATOR SPRING IS INSTALLED REMOVE THE INSTALL...

Page 16: ...e installation arm to installation housing as shown and rotate in arrow direction Ensure that installation sound is heart when installing the closing spring If there is a spring installation motor on the switchgear spring will be installed automatically when LV fuses are closed After the closing spring is installed Earthing switch open closing spring installed LBS open Operation Instructions 14 Ul...

Page 17: ...d Earthing switch open opening spring installed LBS closed OPENINGTHE LBS Press the on button to open the LBS Or plug the remote control cable delivered with the switchgear group to remote control socket and press the on button Position after the LBS is opened Earthing switch open LBS open closing spring idle Ulusoy HMH24 01 Incoming Outgoing Switchgear with LBS User Manual August 2020 www eaton c...

Page 18: ...s open and LBS is open This lock is used in order to prevent earthing switch from closing when there is energy in input switchgears Do not operate LBS if earthing switch is closed Do not operate earthing switch if LBS is closed They are interlocked for user safety Safe Use Switchgear front door can only be placed and removed when the earthing switch is in closed position 16 Ulusoy HMH24 01 Incomin...

Page 19: ...g switch Double check ES contact lubricating LBS can not closed Check the earthing switch if it is closed Then you need to open LBS does not work with electrical commands Check the LV cable connections Check the LV fuses Check the earthing switch Check the DC auxilliary supply Check the DC auxilliary supply polarity Please ensure that the switchgear is not fully manuel Charging motor does not work...

Page 20: ...s to improve the quality of life and the environment through the use of power management technologies and services We provide sustainable solutions that help our customers effectively manage electrical hydraulic and mechanical power more safely more efficiently and more reliably Eaton s 2019 revenues were 21 4 billion and we sell products to customers in more than 175 countries We have approximate...