Figure 5-2
Incorrect installation
● Ensure that the length of the dead space at the end of the process connection is smaller than
its diameter.
● To ensure optimal cleaning of the process plant, install the process connection without
offset (flush-mounted on inside) in the plant.
You can find additional information in the EHEDG Guidelines No. 10 and No. 37.
5.3
Installation (level)
Mounting location
Verify that the mounting location meets the following conditions:
● Accessible
● Close to the measuring point
● Vibration-free
● Within the permitted ambient temperature values
Protect the pressure transmitter from:
● Direct heat radiation
● Rapid temperature fluctuations
● Heavy contamination
● Mechanical damage
● Direct sunlight
Note
Select the height of the mounting flange such that the pressure transmitter is always mounted
below the lowest fill height to be measured.
Requirement
● You have compared the desired operating data with the data on the nameplate.
● You have adhered to the information on the remote seal during its installation.