3.8 mA
22.8 mA
20 mA
20.5 mA
4 mA
3.55 mA
①
Normal operation
②
Lower fault current (factory setting)
③
Lower saturation limit (factory setting)
④
Upper saturation limit (factory setting)
⑤
Upper fault current (factory setting)
9.2.10
Upper fault current [12]
Adjusts the magnitude of the upper fault current
⑤
.
Setting range:
Between upper saturation limit
④
und 22.8 mA
Factory setting:
22.8 mA, or as specified in order
3.8 mA
22.8 mA
20 mA
20.5 mA
4 mA
3.55 mA
①
Normal operation
②
Lower fault current (factory setting)
③
Lower saturation limit (factory setting)
④
Upper saturation limit (factory setting)
⑤
Upper fault current (factory setting)
9.2.11
Lower saturation limit [13]
Sets the lower threshold for the lower saturation limit
③
.
The loop current cannot drop below the set threshold.
Setting range:
Between lower fault current
②
and 4 mA
Factory setting:
3.8 mA, or as specified in order
Parameter assignment
9.2 Parameter assignment over device with display
SITRANS P320/P420 with 4 to 20 mA/HART
Operating Instructions, 11/2019, A5E44852162-AC
125