Device status symbols
Display
– NAMUR NE 107
NAMUR
– HCF
SIMATIC PDM/PLC
Symbol
Device status
Priority *
Symbol
Device status
Priority *
Failure
1
Maintenance alarm
1
Cause: Output signal invalid due to fault in the field device or in the peripherals.
Measure: Maintenance is required immediately.
Maintenance
required
4
Maintenance demanded
2
Cause:Output signal is still valid, but wear reserve is almost exhausted and/or a function will be limited soon.
Measure:Maintenance is strongly recommended as soon as possible.
Maintenance
required
4
Maintenance required
3
Cause: The output signal is still valid. No functional restrictions have been determined but the wear reservice will most likely
be exhausted in the next few weeks.
Measure: Maintenance of device should be planned.
Function test
2
Manual operation
4
Cause: Output signal temporarily invalid (e.g. frozen) due to work being performed on the device.
Measure: Manual mode over HMI or disable the engineering system.
Function test
2
Simulation mode
5
Cause: The output signal does temporarily not reflect the process because the output is based on a simulation value.
Measure: Simulation mode over HMI or disable the engineering system or restart device.
Failure
1
Out of service
6
Cause: The output signal does not represent the process value. The device mode is set to "Out of service".
Measure: Disable "Out of service" and enable normal operation.
Failure
1
(red)
Configuration error
7
Cause: Output signal invalid due to parameter setting, connection error or configuration error in the HW.
Measure: Check hardware configuration of the device over HMI or engineering system.
Diagnostics and troubleshooting
12.1 Device status symbols
SITRANS P320/P420 with 4 to 20 mA/HART
190
Operating Instructions, 11/2019, A5E44852162-AC
Содержание SITRANS P
Страница 10: ...Table of contents SITRANS P320 P420 with 4 to 20 mA HART 10 Operating Instructions 11 2019 A5E44852162 AC ...
Страница 272: ...Abbreviations SITRANS P320 P420 with 4 to 20 mA HART 272 Operating Instructions 11 2019 A5E44852162 AC ...
Страница 280: ...Index SITRANS P320 P420 with 4 to 20 mA HART 280 Operating Instructions 11 2019 A5E44852162 AC ...