The diagnostic status of the simulation selected for each diagnostic is displayed in additional
tabs in the dialog box. The simulated diagnostics is indicated by a check mark in the check box.
End diagnostics simulation
You close the simulation in the "Diagnostics simulation" tab:
● To disable a specific diagnostic action, click "Off" (under the "Action" field).
● To end the diagnostics simulation, click on the "Disable" button.
WARNING
When diagnostics simulation is enabled, diagnostic events of the real process are neither
recorded nor evaluated.
With activated diagnostics simulation, only the simulated diagnostics are displayed on the
device display.
Stop diagnostics simulation immediately after use:
● Click "Disable" in the "Diagnostics simulation" tab before you close the "Diagnostics"
dialog.
● Alternatively, you can restart the device.
9.3.5
Customized characteristic curve
9.3.5.1
Introduction
For special applications, a customized characteristic curve is available.
This application is used, for example, for volume measurement in vessels with unusual shapes.
You define the relationship between inlet pressure and outlet current according to your user-
specific requirements.
You have up to 32 breakpoints available for this, which you enter using the engineering system
and display graphically.
Example
For measurement with the customized characteristic curve, you set the following values, for
example:
Damping value:
2.0 s
Lower range value:
0 bar
Upper range value:
10 bar
Application:
Custom (CUSTM)
Unit:
Cans
Lower scaling point:
0 cans
Parameter assignment
9.3 Parameter assignment over remote operation
SITRANS P320/P420 with 4 to 20 mA/HART
Operating Instructions, 11/2019, A5E44852162-AC
149
Содержание SITRANS P
Страница 10: ...Table of contents SITRANS P320 P420 with 4 to 20 mA HART 10 Operating Instructions 11 2019 A5E44852162 AC ...
Страница 272: ...Abbreviations SITRANS P320 P420 with 4 to 20 mA HART 272 Operating Instructions 11 2019 A5E44852162 AC ...