Two SITRANS P devices are required for multi-channel operation for SIL 3. Operation with one
device is not permitted.
Note
Switching-off of system at high monitoring accuracy
The two transmitters are connected to the process at different positions. Actual differences in
pressure ≥ the total tolerance (safety function) can occur when the process is started up or if
there are other pressure variations. A difference in pressure ≥ the total tolerance (safety
function) will shut down the system.
● Match the monitoring accuracy of the automation system to the process.
● Mount the two transmitters exposed to equal conditions.
10.1.3.1
Device states
The following table provides a definition of the states of the device:
Device state
Description
Error class
Normal mode (4-20 mA)
The safe current output outputs
the measured value within the
defined safety accuracy.
-
Detected failure (safe state)
The safe current output is
≤ 3.6 mA or > 21.5 mA (specified
as failure signal).
(λ
DD
) Rate of dangerous detec‐
ted errors
Dangerous state
A dangerous state exists when a
current output is in the range
4-20 mA and deviates from the
correct process value by more
than the specified safety accura‐
seconds.
(λ
DU
) Rate of dangerous undetec‐
ted errors
10.1.3.2
Safety characteristic values
You can find the safety characteristic values in the SIL Declaration of Conformity.
Note
Useful lifetime
Constant failure rates are assumed for the calculation of PFD/SFF. This assumption is valid for
environmental conditions that are typical for an industrial environment, corresponding to IEC
60654-1 class C (weatherproof locations) with an average long-term temperature of 40°C. After
14 years, however, the failure rates may increase.
Functional Safety
10.1 Safety concept
SITRANS P320/P420 with 4 to 20 mA/HART
162
Operating Instructions, 11/2019, A5E44852162-AC
Содержание SITRANS P
Страница 10: ...Table of contents SITRANS P320 P420 with 4 to 20 mA HART 10 Operating Instructions 11 2019 A5E44852162 AC ...
Страница 272: ...Abbreviations SITRANS P320 P420 with 4 to 20 mA HART 272 Operating Instructions 11 2019 A5E44852162 AC ...
Страница 280: ...Index SITRANS P320 P420 with 4 to 20 mA HART 280 Operating Instructions 11 2019 A5E44852162 AC ...