Modbus holding registers
A.3 Modbus holding registers tables
FC410 with Modbus
Operating Instructions, 02/2016, A5E33120874-AC
137
Modbus
address
Data type /
Size [bytes]
Parameter
Description
Default value
[unit]
Value range Access
level
3014
Unsigned /
4
Alarm Group 2 The following bit is set in case of
active alarm:
•
Bit 0:
Min Frame Temp Exceeded
•
Bit 1:
Max Frame Temp Exceeded
•
Bit 2:
Zero Sigma Limit Exceeded
•
Bit 3:
Zero Offset Limit Exceeded
•
Bit 4:
Quality Of Zero Point
Conditions
•
Bit 5:
Empty Pipe
•
Bit 6:
Sensor Partially Filled
•
Bit 7:
Storage Malfunction
•
Bit 8:
System Internal
•
Bit 14:
Unstable Measurement
Conditions
•
Bit 15:
Auto-filtering enabled
•
Bit 23:
Sensor Startup
-
-
Read Only
Содержание SITRANS FC410
Страница 2: ......
Страница 70: ...Commissioning 6 14 Process variables FC410 with Modbus 68 Operating Instructions 02 2016 A5E33120874 AC ...
Страница 92: ...Troubleshooting FAQs 10 2 Troubleshooting FC410 with Modbus 90 Operating Instructions 02 2016 A5E33120874 AC ...
Страница 142: ...Sensor dimension dependent default settings FC410 with Modbus 140 Operating Instructions 02 2016 A5E33120874 AC ...
Страница 146: ...Zero point adjustment FC410 with Modbus 144 Operating Instructions 02 2016 A5E33120874 AC ...
Страница 150: ...CRC calculation FC410 with Modbus 148 Operating Instructions 02 2016 A5E33120874 AC ...
Страница 152: ...Exception codes E 1 Exception handling FC410 with Modbus 150 Operating Instructions 02 2016 A5E33120874 AC ...
Страница 154: ...Float definition F 1 Float definition FC410 with Modbus 152 Operating Instructions 02 2016 A5E33120874 AC ...