Modbus holding registers
A.3 Modbus holding registers tables
FC410 with Modbus
Operating Instructions, 02/2016, A5E33120874-AC
135
A.3.8
Simulation
Table A- 18 Simulation
Modbus
address
Data type /
Size [bytes]
Parameter
Description
Default value
[unit]
Value range Access
level
2764
Float / 4
Massflow Simulation
Value
Set massflow simulation
value.
The massflow will be set to
this value on all outputs, if
Simulation Mass Flow is
enabled
0 [kg/s]
-1023 to
+1023
Read /
Write
2766
Float / 4
Density Simulation
Value
Set density simulation
value.
The density will be set to
this value on all outputs, if
Simulation Density is
enabled
1000 [kg/m
3
] -20000 to
+20000
Read /
Write
2768
Float / 4
Tube Temperature
Simulation Value
Set tube temperature
simulation value.
The tube temperature will
be set to this value on all
outputs if Simulation Tube
Temperature is enabled
0 [°C]
-50 to +200 Read /
Write
2770
Float / 4
Frame Temperature
Simulation Value
Set frame temperature
simulation value.
The frame temperature will
be set to this value on all
outputs if Simulation Frame
Temperature is enabled
0 [°C]
-50 to +200 Read /
Write
2772
Float / 4
Volumeflow
Simulation Value
Set volume flow simulation
value.
The volume flow will be set
to this value on all outputs,
if Simulation Volume Flow is
enabled
m
3
/s
-65 to +65 Read /
Write
2780
Unsigned /
2
Enable Simulation
Activate simulation.
Select one of the following
values:
•
Bit 0: Massflow
•
Bit 1: Density
•
Bit 2: Volumeflow
•
Bit 3: Tube temperature
•
Bit 4: Frame tempera-
ture
0
0 to 63
Read /
Write
Содержание SITRANS FC410
Страница 2: ......
Страница 70: ...Commissioning 6 14 Process variables FC410 with Modbus 68 Operating Instructions 02 2016 A5E33120874 AC ...
Страница 92: ...Troubleshooting FAQs 10 2 Troubleshooting FC410 with Modbus 90 Operating Instructions 02 2016 A5E33120874 AC ...
Страница 142: ...Sensor dimension dependent default settings FC410 with Modbus 140 Operating Instructions 02 2016 A5E33120874 AC ...
Страница 146: ...Zero point adjustment FC410 with Modbus 144 Operating Instructions 02 2016 A5E33120874 AC ...
Страница 150: ...CRC calculation FC410 with Modbus 148 Operating Instructions 02 2016 A5E33120874 AC ...
Страница 152: ...Exception codes E 1 Exception handling FC410 with Modbus 150 Operating Instructions 02 2016 A5E33120874 AC ...
Страница 154: ...Float definition F 1 Float definition FC410 with Modbus 152 Operating Instructions 02 2016 A5E33120874 AC ...