FC410 with Modbus
Operating Instructions, 02/2016, A5E33120874-AC
117
Modbus holding registers
A
A.1
Modbus addressing model
The device allows read/write access to the following standard Modbus RTU data holding
register blocks:
●
Holding registers (ref. 4x address range)
The minimum value of a writable holding register can be read by adding 10000 to the
Modbus address of the register.
The maximum value of a writable holding register can be read by adding 20000 to the
Modbus address of the register.
The default value of a writable holding register can be read by adding 30000 to the Modbus
address of the register.
A.2
Modbus function codes
This device supports following function codes: 3, 8 and 16.
Function codes 3 and 16 are used for accessing registers, max. 16 registers per read/write
request is accepted.
Function code 8 is used for reading Modbus communication diagnostic information.
Below the various function code are described.
Function code 3 (Read holding registers)
General exceptions:
●
Requesting less than 1 or more than 16 registers => Exception 3 (Illegal data value)
●
Requesting invalid start address or start address with invalid quantity => Exception 2
(Illegal data address)
Application exceptions:
●
Application errors; min/max limit of parameter exceeded; or parameter write-protected =>
Exception 4 (Slave device error)
Holes/register alignment:
●
The read command always returns data if no exception is given.
●
Holes in the holding register map return value zero in all bytes. E.g. reading 2 registers
starting at 4:0004 above will result in 2 bytes of "float B" followed by 2 zeroes.
Содержание SITRANS FC410
Страница 2: ......
Страница 70: ...Commissioning 6 14 Process variables FC410 with Modbus 68 Operating Instructions 02 2016 A5E33120874 AC ...
Страница 92: ...Troubleshooting FAQs 10 2 Troubleshooting FC410 with Modbus 90 Operating Instructions 02 2016 A5E33120874 AC ...
Страница 142: ...Sensor dimension dependent default settings FC410 with Modbus 140 Operating Instructions 02 2016 A5E33120874 AC ...
Страница 146: ...Zero point adjustment FC410 with Modbus 144 Operating Instructions 02 2016 A5E33120874 AC ...
Страница 150: ...CRC calculation FC410 with Modbus 148 Operating Instructions 02 2016 A5E33120874 AC ...
Страница 152: ...Exception codes E 1 Exception handling FC410 with Modbus 150 Operating Instructions 02 2016 A5E33120874 AC ...
Страница 154: ...Float definition F 1 Float definition FC410 with Modbus 152 Operating Instructions 02 2016 A5E33120874 AC ...