Standard mapping 2-3
7SJ61...7SJ63, 7SJ65, 6MD63 PROFIBUS-DP – Bus mapping
C53000-L1840-B006-02
4-7
4.2.1.8 Status
annunciations
•
Ref. to chap. 1.5.7 for additional notes regarding "Stop data transmission".
Offset
Designation of the
SIPROTEC objects
Comments
Internal
object no.
9/0
>No Volt
1 = Binary input “No voltage (fuse blown)" is active
–
9/1
DataStop
1 = "Stop data transmssion" is active
–
9/2
Test mode
1 = Test mode is active
–
9/3
Cntrl Auth (7SJ63, 7SJ65, 6MD63)
Control authority
(0 = REMOTE, 1 = LOCAL)
–
9/4
ModeLOCAL (7SJ63, 7SJ65, 6MD63)
Control mode LOCAL
(0 = LOCKED, 1 = UNLOCKED)
–
9/5
ModeREMOTE
Control mode REMOTE
(0 = LOCKED , 1 = UNLOCKED)
–
9/6
<reserved>
–
9/7
<reserved>
–