Data in the PROFIBUS-DP messages
7SJ61...7SJ63, 7SJ65, 6MD63 PROFIBUS-DP – Bus mapping
C53000-L1840-B006-02
1-5
1.3.3 Metered
measurands
Scaling
The scaling of the metered measurands, which are derived from
measured values, refers to
:
60000 impulses per hour for V = V
nom
and I = I
nom
V
nom
=
N
OMINAL OPERATING VOLTAGE OF PRIMARY EQUIPMENT
(parameter address = 1101)
I
nom
=
N
OMINAL OPERATING CURRENT OF PRIMARY EQUIPMENT
(parameter address = 1102)
Example
In the parameter set is configured:
I
nom
= 100 A und V
nom
= 12.00 kV,
60000 impulses correspond so that:
1 h * 100 A * 12 kV *
3
= 2078.46 kWh
Note
•
The type of the update (cyclic, with or without deletion) and the
update interval must be programmed for the metered measurands
(except for the operating hours meter) with the parameterization
software DIGSI.
•
The scaling of the metered measurands at binary inputs ("Wp(puls)"
and "Wq(puls)") depends on the externally connected pulse
generator.
Содержание SIPROTEC4 6MD63
Страница 6: ...Revision index 7SJ61 7SJ63 7SJ65 6MD63 PROFIBUS DP Bus mapping C53000 L1840 B006 02 iv ...
Страница 56: ...Standard mapping 2 3 7SJ61 7SJ63 7SJ65 6MD63 PROFIBUS DP Bus mapping C53000 L1840 B006 02 4 10 ...
Страница 62: ...Standard mapping 2 4 7SJ61 7SJ63 7SJ65 6MD63 PROFIBUS DP Bus mapping C53000 L1840 B006 02 5 16 ...
Страница 64: ...Glossary 7SJ61 7SJ63 7SJ65 6MD63 PROFIBUS DP Bus mapping C53000 L1840 B006 02 6 2 ...
Страница 66: ...Index 7SJ61 7SJ63 7SJ65 6MD63 PROFIBUS DP Bus mapping C53000 L1840 B006 02 7 2 ...