Standard mapping 2-1
7SJ61...7SJ63, 7SJ65, 6MD63 PROFIBUS-DP – Bus mapping
C53000-L1840-B006-02
2-9
2.2.1.14 Thermal overload protection
Offset
Designation of the
SIPROTEC objects
Comments
Internal
object no.
15/0
49 O/L OFF
1 = Thermal overload protection is switched OFF
1511
15/1
49 O/L I Alarm
1 = 49 Overload current alarm (I alarm)
1515
15/2
49 O/L <Theta> Alarm
1 = 49 Overload alarm! Near thermal TRIP
1516
15/3
49 Windings O/L
1 = 49 Winding overload
1517
15/4
49 Th O/L TRIP
1 = 49 Thermal overload TRIP
1521
15/5
<reserved>
–
2.2.1.15 Motor start protection
Offset
Designation of the
SIPROTEC objects
Comments
Internal
object no.
15/6
>66 emerg. start
1 = Binary input “Emergency start“ is active
4823
15/7
66 OFF
1 = Motor start protection is switched OFF
4824
16/0
66 TRIP
1 = Motor start protection TRIP
4827
2.2.1.16 Startup supervision
Offset
Designation of the
SIPROTEC objects
Comments
Internal
object no.
16/1
START-SUP OFF
1 = Startup supervision is switched OFF
6811
16/2
START-SUP OFF
1 = Startup supervision TRIP
6821
16/3
Rotor locked
1 = Rotor locked
6822
16/4
START-SUP pu
1 = Startup supervision Pickup
6823
2.2.1.17 Trip coil monitor
Offset
Designation of the
SIPROTEC objects
Comments
Internal
object no.
16/5
FAIL: Trip cir.
1 = 74TC Failure trip circuit
6865
2.2.1.18 Cold load pickup setup
Offset
Designation of the
SIPROTEC objects
Comments
Internal
object no.
16/6
CLP OFF
1 = Cold-load-pickup is switched OFF
1994
16/7
CLP BLOCKED
1 = Cold-load-pickup is BLOCKED
1995
17/0
CLP running
1 = Cold-load-pickup is RUNNING
1996
17/1
Dyn set. ACTIVE
1 = Dynamic settings are ACTIVE
1997
Содержание SIPROTEC4 6MD63
Страница 6: ...Revision index 7SJ61 7SJ63 7SJ65 6MD63 PROFIBUS DP Bus mapping C53000 L1840 B006 02 iv ...
Страница 56: ...Standard mapping 2 3 7SJ61 7SJ63 7SJ65 6MD63 PROFIBUS DP Bus mapping C53000 L1840 B006 02 4 10 ...
Страница 62: ...Standard mapping 2 4 7SJ61 7SJ63 7SJ65 6MD63 PROFIBUS DP Bus mapping C53000 L1840 B006 02 5 16 ...
Страница 64: ...Glossary 7SJ61 7SJ63 7SJ65 6MD63 PROFIBUS DP Bus mapping C53000 L1840 B006 02 6 2 ...
Страница 66: ...Index 7SJ61 7SJ63 7SJ65 6MD63 PROFIBUS DP Bus mapping C53000 L1840 B006 02 7 2 ...