Standard mapping 2-2
7SJ61...7SJ63, 7SJ65, 6MD63 PROFIBUS-DP – Bus mapping
C53000-L1840-B006-02
3-10
3.2.2 Measured
values
•
Ref. to chap. 1.3.2 for additional notes regarding scaling of measured values.
3.2.2.1
Recorded measured values
Offset
Designation of the
SIPROTEC objects
Comments
Scaling
(32767 corresponds to ...)
Internal
object no.
16
Ia =
Ia
3276.7 A
601
18
Ib =
Ib
3276.7 A
602
20
Ic =
Ic
3276.7 A
603
22
In =
In
3276.7 A
604
24
I1 =
I1 (positive sequence)
3276.7 A
605
26
I2 =
I2 (negative sequence)
3276.7 A
606
28
<Theta> Rotor
Temperature of rotor
327.67 %
805
30
<Theta> Stator
Temperature of stator
327.67 %
806
3.2.2.2
Measured values – mean values
Offset
Designation of the
SIPROTEC objects
Comments
Scaling
(32767 corresponds to ...)
Internal
object no.
32
I1 dmd =
I1 (positive sequence) demand
3276.7 A
833
34
<reserved>
–
3.2.3 Metered
measurands
•
Ref. to chap. 1.3.3 for additional notes regarding scaling of metered measurands.
Offset
Designation of the
SIPROTEC objects
Comments
Scaling
(2
31
-1 of the unsigned long-
value corresponds to ...)
Internal
object no.
36
Wp(puls) =
Pulsed Energy Wp (active)
(metering impulses at binary input)
2
31
-1 impulses
888
40
Wq(puls) =
Pulsed Energy Wq (reactive)
(metering impulses at binary input)
2
31
-1 impulses
889
44
Op.Hours=
Counter of operating hours of the
primary equipment
2
31
-1 hours
1020
Содержание SIPROTEC4 6MD63
Страница 6: ...Revision index 7SJ61 7SJ63 7SJ65 6MD63 PROFIBUS DP Bus mapping C53000 L1840 B006 02 iv ...
Страница 56: ...Standard mapping 2 3 7SJ61 7SJ63 7SJ65 6MD63 PROFIBUS DP Bus mapping C53000 L1840 B006 02 4 10 ...
Страница 62: ...Standard mapping 2 4 7SJ61 7SJ63 7SJ65 6MD63 PROFIBUS DP Bus mapping C53000 L1840 B006 02 5 16 ...
Страница 64: ...Glossary 7SJ61 7SJ63 7SJ65 6MD63 PROFIBUS DP Bus mapping C53000 L1840 B006 02 6 2 ...
Страница 66: ...Index 7SJ61 7SJ63 7SJ65 6MD63 PROFIBUS DP Bus mapping C53000 L1840 B006 02 7 2 ...