7SJ61...7SJ63, 7SJ65, 6MD63 PROFIBUS-DP – Bus mapping
C53000-L1840-B006-02
5-11
5
Standard mapping 2-4
Standard mapping 2-4
5
5.1
Message in output direction
5.1.1 Double commands (with checkback indication)
Offset
Designation of the
SIPROTEC objects
Comments
Internal
object no.
0/0
Q0 ON/OFF
OFF
0/1
Q0 ON/OFF
ON
Impulse output,
3 relays (2-pole ON, 1-pole OFF)
–
0/2
Q1 ON/OFF
OFF
0/3
Q1 ON/OFF
ON
Impulse output,
2 relays, 1-pole
–
0/4
Q8 ON/OFF
OFF
0/5
Q8 ON/OFF
ON
Impulse output,
2 relays, 1-pole
–
5.1.2 Single commands (without checkback indication)
•
Ref. to chap. 1.5.1 and 1.6 for additional notes.
Offset
Designation of the
SIPROTEC objects
Comments
Internal
object no.
0/6
Output channel E1 (UsrSC5)
OFF
0/7
Output channel E1 (UsrSC5)
ON
Impulse output,
1 relay, 1-pole
–
5.1.3 Internal
commands
•
Ref. to chap. 1.5.3 for additional notes regarding "Changing the setting group".
Offset
Designation of the
SIPROTEC objects
Comments
Internal
object no.
1/0
Setting group A
1/1
Setting group A
Activation of setting group A
53
1/2
Setting group B
1/3
Setting group B
Activation of setting group B
54
Содержание SIPROTEC4 6MD63
Страница 6: ...Revision index 7SJ61 7SJ63 7SJ65 6MD63 PROFIBUS DP Bus mapping C53000 L1840 B006 02 iv ...
Страница 56: ...Standard mapping 2 3 7SJ61 7SJ63 7SJ65 6MD63 PROFIBUS DP Bus mapping C53000 L1840 B006 02 4 10 ...
Страница 62: ...Standard mapping 2 4 7SJ61 7SJ63 7SJ65 6MD63 PROFIBUS DP Bus mapping C53000 L1840 B006 02 5 16 ...
Страница 64: ...Glossary 7SJ61 7SJ63 7SJ65 6MD63 PROFIBUS DP Bus mapping C53000 L1840 B006 02 6 2 ...
Страница 66: ...Index 7SJ61 7SJ63 7SJ65 6MD63 PROFIBUS DP Bus mapping C53000 L1840 B006 02 7 2 ...