Mounting And Commissioning
3.3 Commissioning
SIPROTEC, 7VU681, User Manual
C53000-G1176-C368-1, Release Date 07.2012
88
Figure 3-15
Testing of the binary inputs and outputs - example
Changing the Operating State
To change the condition of a hardware component, click on the associated switching field in the
Scheduled
column.
Password No. 6 (if activated during configuration) will be requested before the first hardware modification is
allowed. After entry of the correct password a condition change will be executed. Further condition changes
remain possible while the dialog box is open.
Test of the Binary Outputs
Each individual output relay can be energized allowing a check of the wiring between the output relay of the
7VU681 and the system, without having to generate the message that is assigned to the relay. As soon as the
first change of state for any of the output relays is initiated, all output relays are separated from the internal
device functions, and can only be operated by the hardware test function. This means, that e.g. a TRIP
command coming from a control command from the operator panel to an output relay cannot be executed.
Proceed as follows in order to check the output relay :
Ensure that the switching of the output relay can be executed without danger (see above under DANGER!).
• Each output relay must be tested via the corresponding
Scheduled
-cell in the dialog box.
• The test sequence must be terminated (refer to margin heading "Exiting the Procedure"), to avoid the
initiation of inadvertent switching operations by further tests.
Test of the Binary Inputs
To test the wiring between the plant and the binary inputs of the 7VU681 the condition in the system which
initiates the binary input must be generated and the response of the device checked.
To do this, the dialog box
Hardware Test
must again be opened to view the physical state of the binary inputs.
The password is not yet required.
Содержание SIPROTEC 7VU681
Страница 8: ...Preface SIPROTEC 7VU681 User Manual C53000 G1176 C368 1 Release Date 07 2012 8 ...
Страница 12: ...Contents SIPROTEC 7VU681 User Manual C53000 G1176 C368 1 Release Date 07 2012 12 ...
Страница 100: ...Literature SIPROTEC 7VU683 User Manual C53000 G1176 C368 1 Release Date 07 2012 100 ...
Страница 110: ...Appendix A 4 Dimension SIPROTEC 7VU681 User Manual C53000 G1176 C368 1 Release Date 07 2012 110 ...
Страница 112: ...Index SIPROTEC 7VU681 User Manual C53000 G1176 C368 1 Release Date 07 2012 112 ...