Mounting And Commissioning
3.1 Mounting And Connections
SIPROTEC, 7VU681, User Manual
C53000-G1176-C368-1, Release Date 07.2012
66
Table 3-3
Jumper position of the quiescent state of the Life contact on the C-CPU-2 processor module
Table 3-4
Jumper setting of the control voltages of binary inputs BI1 to BI5 on the C-CPU-2 processor
module
1)
Factory settings for devices with rated power supply voltages of 24 VDC to 125 VDC
2)
Factory settings for devices with power supply voltages of 110 VDC to 250 VDC and 115/230 VAC
3)
Use only with pickup voltages 220 or 250 VDC
The R485 interface can be converted into an RS232 interface by modifying the jumpers.
Jumpers X105 to X110 must be set to the same position !
Table 3-5
Jumper Settings of the Integrated RS232/RS485 Interface on the C-CPU-2 Board
The jumpers are preset at the factory according to the configuration ordered.
With interface RS232 jumper X111 is needed to activate CTS which enables the communication with the
modem.
Table 3-6
Jumper setting for CTS (flow control) on the C-CPU-2 processor module
1)
Default setting of releases 7VU68.../BB
Jumper setting 2-3:
The connection to the modem is usually established with a star coupler or fibre-optic
converter. Therefore the modem control signals according to RS232 standard DIN 66020 are not available.
Modem signals are not required since the connection to the SIPROTEC? 4 devices is always operated in the
half-duplex mode. Please use the connection cable with order number 7XV5100-4.
Jumper setting 1-2:
This setting makes the modem signals available, i. e. for a direct RS232-connection
between the SIPROTEC 4 device and the modem this setting can be selected optionally. We recommend use
of a standard RS232 modem connection cable (converter 9-pole on 25-pole).
Jumper
Nominal Voltage
Open in the quiescent
state
(NO contact)
Closed in the quiescent
state
(NC contact)
Presetting
X40
1-2
2-3
2-3
Binary inputs
Jumper
17 V Threshold
73V Threshold
154V Threshold
BI1
X21
1-2
2-3
3-4
BI2
X22
1-2
2-3
3-4
BI3
X23
1-2
2-3
3-4
BI4
X24
1-2
2-3
3-4
BI5
X25
1-2
2-3
3-4
Jumper
/CTS from interface RS232
/CTS triggered by /RTS
X103 to X104
1-2
1-2
X105 to X110
1-2
2-3
Jumper
/CTS from interface RS232
/CTS triggered by /RTS
X111
1-2
2-3
Содержание SIPROTEC 7VU681
Страница 8: ...Preface SIPROTEC 7VU681 User Manual C53000 G1176 C368 1 Release Date 07 2012 8 ...
Страница 12: ...Contents SIPROTEC 7VU681 User Manual C53000 G1176 C368 1 Release Date 07 2012 12 ...
Страница 100: ...Literature SIPROTEC 7VU683 User Manual C53000 G1176 C368 1 Release Date 07 2012 100 ...
Страница 110: ...Appendix A 4 Dimension SIPROTEC 7VU681 User Manual C53000 G1176 C368 1 Release Date 07 2012 110 ...
Страница 112: ...Index SIPROTEC 7VU681 User Manual C53000 G1176 C368 1 Release Date 07 2012 112 ...