Function
2.2 Protection
SIPROTEC, 7VU681, User Manual
C53000-G1176-C368-1, Release Date 07.2012
49
2.2.1.1
Settings
2.2.1.2
Information List
Addr.
Parameter
Setting Options
Default Setting
Comments
Protection Functions->General
9000
Phase Overcurrent
ON
OFF
OFF
Protection Functions -> Voltage Control
9002
Ph-Ph Undervoltage
Threshold
1V..125V, 0V
70 V
9003
U2 Overvoltage Threshold
1V..125V,
∞
8 V
Protection Functions -> Phase O/C
9001
Compound Voltage Control
YES
NO
YES
9004
Phase Overcurrent-1
0.1A..35 A
3 A
9005
Phase Overcurrent-1 Time
Delay
0s..60s,
∞
0.5s
9006
Phase Overcurrent-2
0.1A..35 A
5 A
9007
Phase Overcurrent-2 Time
Delay
0s..60s,
∞
0.1s
No.
Information
Type
Function No.
Inf.NO.
17822
>Block PhaseO/C
SP
17939
PhaseO/C ACTIVE
OUT
17823
PhaseO/C OFF
OUT
17824
PhaseO/C BLK
OUT
17827
PhaseO/C-1 PU
OUT
17828
PhaseO/C-1 Trip
OUT
200
44
17829
PhaseO/C-2 PU
OUT
17830
PhaseO/C-2 Trip
OUT
200
46
17981
Ph.O/C ON/OFF
IntSP
200
85
Содержание SIPROTEC 7VU681
Страница 8: ...Preface SIPROTEC 7VU681 User Manual C53000 G1176 C368 1 Release Date 07 2012 8 ...
Страница 12: ...Contents SIPROTEC 7VU681 User Manual C53000 G1176 C368 1 Release Date 07 2012 12 ...
Страница 100: ...Literature SIPROTEC 7VU683 User Manual C53000 G1176 C368 1 Release Date 07 2012 100 ...
Страница 110: ...Appendix A 4 Dimension SIPROTEC 7VU681 User Manual C53000 G1176 C368 1 Release Date 07 2012 110 ...
Страница 112: ...Index SIPROTEC 7VU681 User Manual C53000 G1176 C368 1 Release Date 07 2012 112 ...