Function
2.2 Protection
SIPROTEC, 7VU681, User Manual
C53000-G1176-C368-1, Release Date 07.2012
51
2.2.2.1
Settings
2.2.2.2
Information List
Addr.
Parameter
Setting Options
Default Setting
Comments
Protection Functions-> General
9010
Zero Sequence
Overcurrent
ON
OFF
OFF
9018
3I0/IE Assignment
IE
3I0
3I0
Protection Functions -> Voltage Control
9012
3U0 Overvoltage
Threshold
1V..200V
30V
Protection Functions -> Zero Sequ. O/C
9011
3U0 Control
Yes
No
Yes
9013
Zerosequ. Overcurrent-1
0.1A..35A
3A
9014
Zerosequ. Overcurrent-1
Time Delay
0s..60s,
∞
0.5s
9015
Zerosequ. Overcurrent-2
0.1A..35A
5A
9016
Zerosequ. Overcurrent-1
Time Delay
0s..60s,
∞
0.1s
No.
Information
Type
Function No.
Inf.No.
17831
>Block ZSOC
SP
17940
ZSOC ACTIVE
OUT
17832
ZSOC OFF
OUT
17833
ZSOC BLK
OUT
17836
ZSOC-1 PU
OUT
17837
ZSOC-1 Trip
OUT
200
48
17838
ZSOC-2 PU
OUT
17839
ZSOC-2 Trip
OUT
200
50
17982
ZSOC ON/OFF
IntSP
200
86
Содержание SIPROTEC 7VU681
Страница 8: ...Preface SIPROTEC 7VU681 User Manual C53000 G1176 C368 1 Release Date 07 2012 8 ...
Страница 12: ...Contents SIPROTEC 7VU681 User Manual C53000 G1176 C368 1 Release Date 07 2012 12 ...
Страница 100: ...Literature SIPROTEC 7VU683 User Manual C53000 G1176 C368 1 Release Date 07 2012 100 ...
Страница 110: ...Appendix A 4 Dimension SIPROTEC 7VU681 User Manual C53000 G1176 C368 1 Release Date 07 2012 110 ...
Страница 112: ...Index SIPROTEC 7VU681 User Manual C53000 G1176 C368 1 Release Date 07 2012 112 ...