Function
2.3 Monitor Function
SIPROTEC, 7VU681, User Manual
C53000-G1176-C368-1, Release Date 07.2012
57
Figure 2-30
Logic Diagram of Line PT Broken Wire Supervision
Logic of line PT broken wire supervision:
1. For device 7VU681, Line1 PT broken wire will be unavailable if the parameter
213 PT Connection of Line1
is set to
Not Connected
; Line2 PT broken wire will be unavailable if the parameter
214 PT Connection
of Line2
is set to
Not Connected
.
2. If the parameter
213 PT Connection of Line1
is set to
Va-b transformer, Vb-c transformer
or
Vc-a
transformer
, the value of dead line equals the value of
8903 Line Dead Voltage Threshold
; if the
parameter
213
PT Connection of Line1
is set to
Va transformer, Vb transformer
or
Vc transformer
, the
value of dead line equals the value of
8903 Line Dead Voltage Threshold
/1.732. It is same with Line2.
2.3.1.1
Settings
2.3.1.2
Information List
Addr.
Settings
Setting Options
Default Setting
Comments
Supervision
9101
PTBroken Wire
ON
OFF
ON
No.
Information
Type
Function No.
Inf. No.
17737
Busbar PT Brk.
OUT
17729
Busbar1 PT Broken
OUT
17730
Busbar2 PT Broken
OUT
17731
Line1 PT Broken
OUT
17732
Line2 PT Broken
OUT
Содержание SIPROTEC 7VU681
Страница 8: ...Preface SIPROTEC 7VU681 User Manual C53000 G1176 C368 1 Release Date 07 2012 8 ...
Страница 12: ...Contents SIPROTEC 7VU681 User Manual C53000 G1176 C368 1 Release Date 07 2012 12 ...
Страница 100: ...Literature SIPROTEC 7VU683 User Manual C53000 G1176 C368 1 Release Date 07 2012 100 ...
Страница 110: ...Appendix A 4 Dimension SIPROTEC 7VU681 User Manual C53000 G1176 C368 1 Release Date 07 2012 110 ...
Страница 112: ...Index SIPROTEC 7VU681 User Manual C53000 G1176 C368 1 Release Date 07 2012 112 ...