Technical Data
4.1 General
SIPROTEC, 7VU681, User Manual
C53000-G1176-C368-1, Release Date 07.2012
96
4.1
General
Current Input
4.2
Rated electrical parameters
4.3
Functional Data
4.3.1
ATS
Recommended permanent operating
temperature
-5~55
Limiting temporary (transient) operating
temperature
-20~70°C
Limit temperatures during transport
-25~70°C
Rated auxiliary direct voltage:
220V,110V
Tolerance
+20%,-20%
Alternating Voltage
80~125/3V(Un)
Rated current
5 A,1 A (In)
Rated frequency
50Hz,60Hz
Overload capability::
Current overload capability
4 IN continuous
30 IN for 10 s
100 IN for 1 s
Voltage path overload capacity
230 V continuous
Power consumption:
Current
Approx. 0.3 VA(In=5 A)
Approx. 0.05 VA(In=1 A)
Voltage
Approx. 0.10 VA/Phase
Power Consumption:
Quiescent, Approx. 8 W
Energized, Approx. 15 W
Time Tolerance of ATS
< 50ms
Frequency Tolerance
<0.02Hz
Voltage Tolerance
<0.2V
Current Tolerance
<0.01In
Frequency Range
0Hz ~ 66Hz
External BI filter time
10ms