MofPU = 1 bis 1.94
MofPU = 2 bis 4.75
MofPU = 5 bis 7.75
MofPU = 8 bis 20
1.31
1.81
3.25
4.75
6.25
7.75
13.00
20.00
1.38
1.88
14.00
1.44
1.94
The value pairs are entered at address 1531
MofPU Res T/Tp
to recreate the reset curve. The following
must be observed:
•
The current values entered should be those from
, along with the matching times. Deviating
values
Ι
/
Ι
p are rounded. This, however, will not be indicated.
Current flows greater than the highest current value entered will not lead to a prolongation of the reset
time. The reset curve (see
, left side) is parallel to the current axis, beginning with the largest
current point.
Current flows which are less than the smallest current value entered will not lead to a reduction of the
reset time. The reset curve (see
, left side) is parallel to the current axis, beginning with the
smallest current point.
Table 2-10
Preferential values of standardized currents for user-defined dropout curves
MofPU = 1 bis 0.86
MofPU = 0.84 bis 0.67
MofPU = 0.66 bis 0.38
MofPU = 0.34 bis 0.00
1.00
0.93
0.84
0.75
0.66
0.53
0.34
0.16
0.99
0.92
0.83
0.73
0.64
0.50
0.31
0.13
0.98
0.91
0.81
0.72
0.63
0.47
0.28
0.09
0.97
0.90
0.80
0.70
0.61
0.44
0.25
0.06
0.96
0.89
0.78
0.69
0.59
0.41
022
0.03
0.95
0.88
0.77
0.67
0.56
0.38
0.19
0.00
0.94
0.86
[anwenderkennl-260602-kn, 1, en_US]
Figure 2-35
Using a user-defined curve
Inrush Restraint
When applying the protection device to transformers where high inrush currents are to be expected, the
7SJ62/64 can make use of an inrush restraint function for the directional overcurrent elements
67-1
PICKUP
,
67-TOC PICKUP
,
67N-1 PICKUP
and
67N-TOC PICKUP
as well as the non-directional overcur-
rent elements. The inrush restraint option is enabled or disabled in 2201
INRUSH REST.
(in the settings
option non-directional time overcurrent protection). The characteristic values of the inrush restraint are
already listed in the section discussing the non-directional time overcurrent (Section
).
Functions
2.3 Directional Overcurrent Protection 67, 67N
104
SIPROTEC 4, 7SJ62/64, Manual
C53000-G1140-C207-8, Edition 08.2016
Содержание SIPROTEC 4
Страница 8: ...8 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Страница 18: ...18 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Страница 30: ...30 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Страница 540: ...540 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Страница 594: ...594 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Страница 720: ...720 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...