Addr. Parameter
Function
C
Setting Options
Default Setting
Comments
4306 MAX.WARM
STARTS
48/66 Motor-
prot
1 .. 4
2
Maximum Number of
Warm Starts
4307 #COLD-#WARM
48/66 Motor-
prot
1 .. 2
1
Number of Cold Starts -
Warm Starts
4308 Kτ at STOP
48/66 Motor-
prot
0.2 .. 100.0
5.0
Extension of Time
Constant at Stop
4309 Kτ at RUNNING
48/66 Motor-
prot
0.2 .. 100.0
2.0
Extension of Time
Constant at Running
4310 T MIN. INHIBIT
48/66 Motor-
prot
0.2 .. 120.0 min
6.0 min
Minimum Restart Inhibit
Time
4311 ROTOR OVERLOAD 48/66 Motor-
prot
ON
OFF
Alarm Only
ON
Rotor Overload Protection
4401 Load Jam Prot.
48/66 Motor-
prot
OFF
ON
Alarm Only
OFF
Load Jam Protection
4402 Load Jam I>
48/66 Motor-
prot
1A
0.50 .. 12.00 A
2.00 A
Load Jam Tripping
Threshold
5A
2.50 .. 60.00 A
10.00 A
4403 TRIP DELAY
48/66 Motor-
prot
0.00 .. 600.00 sec
1.00 sec
Load Jam Trip Delay
4404 I Alarm
48/66 Motor-
prot
1A
0.50 .. 12.00 A
1.80 A
Load Jam Alarm
Threshold
5A
2.50 .. 60.00 A
9.00 A
4405 ALARM DELAY
48/66 Motor-
prot
0.00 .. 600.00 sec
1.00 sec
Load Jam Alarm Delay
4406 T Start Blk.
48/66 Motor-
prot
0.00 .. 600.00 sec
10.00 sec
Load Jam Blocking after
motor start
5001 FCT 59
27/59 O/U Volt.
OFF
ON
Alarm Only
OFF
59 Overvoltage Protec-
tion
5002 59-1 PICKUP
27/59 O/U Volt.
40 .. 260 V
110 V
59-1 Pickup
5003 59-1 PICKUP
27/59 O/U Volt.
40 .. 150 V
110 V
59-1 Pickup
5004 59-1 DELAY
27/59 O/U Volt.
0.00 .. 100.00 sec;
∞
0.50 sec
59-1 Time Delay
5005 59-2 PICKUP
27/59 O/U Volt.
40 .. 260 V
120 V
59-2 Pickup
5006 59-2 PICKUP
27/59 O/U Volt.
40 .. 150 V
120 V
59-2 Pickup
5007 59-2 DELAY
27/59 O/U Volt.
0.00 .. 100.00 sec;
∞
0.50 sec
59-2 Time Delay
5015 59-1-V2 PICKUP
27/59 O/U Volt.
2 .. 150 V
30 V
59-1 Pickup Overvoltage
(neg. seq.)
5016 59-2-V2 PICKUP
27/59 O/U Volt.
2 .. 150 V
50 V
59-2 Pickup Overvoltage
(neg. seq.)
5017A 59-1 DOUT RATIO
27/59 O/U Volt.
0.90 .. 0.99
0.95
59-1 Dropout Ratio
5018A 59-2 DOUT RATIO
27/59 O/U Volt.
0.90 .. 0.99
0.95
59-2 Dropout Ratio
5019 59-1 PICKUP V1
27/59 O/U Volt.
40 .. 150 V
110 V
59-1 Pickup V1
5020 59-2 PICKUP V1
27/59 O/U Volt.
40 .. 150 V
120 V
59-2 Pickup V1
5101 FCT 27
27/59 O/U Volt.
OFF
ON
Alarm Only
OFF
27 Undervoltage Protec-
tion
5102 27-1 PICKUP
27/59 O/U Volt.
10 .. 210 V
75 V
27-1 Pickup
Functions, Settings, Information
F.2 Settings
SIPROTEC 4, 7SJ62/64, Manual
633
C53000-G1140-C207-8, Edition 08.2016
Содержание SIPROTEC 4
Страница 8: ...8 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Страница 18: ...18 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Страница 30: ...30 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Страница 540: ...540 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Страница 594: ...594 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Страница 720: ...720 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...