The following settings are made:
IStart/IMOTnom
= 4.9
I MOTOR NOMINAL
= 0.6 A
T START MAX
= 8.5 s
MAX.WARM STARTS
= 2
#COLD-#WARM
= 1
For the rotor temperature equilibrium time, (address 4304) a setting time of approx.
T Equal
= 1 min has
proven to be a good value. The value for the minimum inhibit time
T MIN. INHIBIT
depends on the motor
manufacturer, or by the user's requirements. It must in any case be higher than 4304
T Equal
. In this
example, a value has been chosen that reflects the thermal replica (
T MIN. INHIBIT
= 6.0 min).
The motor manufacturer's, or the requirements also determine also the extension factor for the time constant
during cool-down, especially with the motor stopped. Where no other specifications are made, the following
settings are recommended:
Kτ at STOP
= 5 and
Kτ at RUNNING
= 2.
For a proper functioning, it is also important that the CT values and the current threshold for distinction
between stopped and running motor (address 212
BkrClosed I MIN
, recommended setting ≈ 0.1
Ι
MOT.NOM
)
have been set correctly. An overview of parameters and their default settings is generally given in the setting
tables.
Temperature Behavior during Changing Operating States
For a better understanding of the above considerations several possible operating ranges in two different
operating areas will be discussed in the following paragraph. Settings indicated above are to be used prevaling
3 cold and 2 warm startup attempts have resulted in the restart limit reaching 66.7%.
A) Below the thermal restarting limit:
•
A normal startup brings the machine into a temperature range below the thermal restarting limit and the
machine is stopped. The stop launches the equilibrium time 4304
T Equal
and generates the message
66 TRIP
. The equilibrium time expires and the message
66 TRIP
is cleared. During the time
T Equal
the thermal replica remains "frozen" (see
•
A normal startup brings the machine into a temperature range below the thermal restarting limit, the
machine is stopped and is started by an emergency startup without waiting for the equilibrium time to
expire. The equilibrium time is reset, the thermal replica is released and
66 TRIP
is reported as going
Functions
2.8 Motor Protection
SIPROTEC 4, 7SJ62/64, Manual
155
C53000-G1140-C207-8, Edition 08.2016
Содержание SIPROTEC 4
Страница 8: ...8 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Страница 18: ...18 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Страница 30: ...30 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Страница 540: ...540 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Страница 594: ...594 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Страница 720: ...720 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...