[anlaufbeispiele-a-260602-kn, 1, en_US]
Figure 2-59
Startups according to examples A.1 and A.2
B) Above the thermal restarting limit:
•
A startup brings the machine from load operation into a temperature range far above the thermal
restarting limit and the machine is stopped. The minimum inhibit time and the equilibrium time are
started and
66 TRIP
is reported. The temperature cool-down below the restarting limit takes longer
than 4310
T MIN. INHIBIT
and 4304
T Equal
, so that the time passing until the temperature falls
below the temperature limit is the decisive factor for clearing the message
66 TRIP
. The thermal replica
remains "frozen" while the equilibrium time expires (see
•
A startup brings the machine from load operation into a temperature range just above the thermal
restarting limit and the machine is stopped. The minimum inhibit time and the equilibrium time are
started and
66 TRIP
is reported. Although the temperature soon falls below the restarting limit, the
blocking
66 TRIP
is preserved until the equilibrium time and the minimum inhibit time have expired
(see
, to the right).
Functions
2.8 Motor Protection
156
SIPROTEC 4, 7SJ62/64, Manual
C53000-G1140-C207-8, Edition 08.2016
Содержание SIPROTEC 4
Страница 8: ...8 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Страница 18: ...18 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Страница 30: ...30 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Страница 540: ...540 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Страница 594: ...594 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Страница 720: ...720 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...