Power Protection Application with Flexible Protection Function
). If the checkmark of a function is removed, all
settings and configurations made previously will be lost. After re-selecting the function, all settings and
configurations are in default setting. Setting of the flexible function is done in DIGSI under “Parameters”,
“Additional Functions” and “Settings”“. The configuration is done as usual under “Parameters” and “Configura-
tion”.
Settings
Addr.
Parameter
Setting Options
Default Setting
Comments
103
Grp Chge OPTION
Disabled
Enabled
Disabled
Setting Group Change Option
104
OSC. FAULT REC.
Disabled
Enabled
Enabled
Oscillographic Fault Records
112
Charac. Phase
Disabled
Definite Time
TOC IEC
TOC ANSI
User Defined PU
User def. Reset
Definite Time
50/51
113
Charac. Ground
Disabled
Definite Time
TOC IEC
TOC ANSI
User Defined PU
User def. Reset
Definite Time
50N/51N
115
67/67-TOC
Disabled
Definite Time
TOC IEC
TOC ANSI
User Defined PU
User def. Reset
Definite Time
67, 67-TOC
116
67N/67N-TOC
Disabled
Definite Time
TOC IEC
TOC ANSI
User Defined PU
User def. Reset
Definite Time
67N, 67N-TOC
117
Coldload Pickup
Disabled
Enabled
Disabled
Cold Load Pickup
122
InrushRestraint
Disabled
Enabled
Disabled
2nd Harmonic Inrush Restraint
127
50 1Ph
Disabled
Enabled
Disabled
50 1Ph
130
S.Gnd.F.Dir.Ch
cos φ / sin φ
V0/I0 φ mea.
cos φ / sin φ
(sens.) Ground fault dir. character-
istic
2.1.1.3
Functions
2.1 General
34
SIPROTEC 4, 7SJ62/64, Manual
C53000-G1140-C207-8, Edition 08.2016
Содержание SIPROTEC 4
Страница 8: ...8 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Страница 18: ...18 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Страница 30: ...30 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Страница 540: ...540 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Страница 594: ...594 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Страница 720: ...720 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...