unless an inrush has been recognized or inrush restraint is active. If the inrush restraint feature is enabled, and
an inrush condition exists, no tripping takes place, but a message is recorded and displayed indicating when
the overcurrent element time delay elapses. Trip signals and other flags for each element are issued when the
element times out. The dropout value is roughly equal to 95% of the pickup value for currents > 0.3
Ι
Nom
.
Pickup can be stabilized by setting dropout times 1518
67 T DROP-OUT
or 1618
67N T DROP-OUT
. This
time is started and maintains the pickup condition if the current falls below the threshold. Therefore, the func-
tion does not drop out at high speed. The trip-command delay time
50-1 DELAY
or
50N-1 DELAY
continues
in the meantime. After the dropout delay time has elapsed, the pickup is reported OFF and the trip delay time
is reset unless the threshold
50-1 PICKUP
or
50N-1 PICKUP
has been exceeded again. If the threshold is
exceeded again during the dropout delay time, the time is canceled. The trip-command delay time
50-1
DELAY
or
50N-1 DELAY
continues in the meantime. Should the threshold value be exceeded after its expiry,
the trip command is issued immediately. If the threshold value is not exceeded at this time, there will be no
reaction. If the threshold value is exceeded again after expiry of the trip-command delay time, while the
dropout delay time is still running, tripping occurs immediately.
The inrush restraint of the overcurrent elements
50-1 PICKUP
or
50N-1 PICKUP
is disabled via configu-
rable dropout times if an inrush pickup occurs, because the occurrence of an inrush does not constitute an
intermittent fault.
Each of these elements can be directional or non-directional (non-directional from V4.81 on).
These elements can be blocked by the automatic reclosure function (AR).
The following figure shows by way of an example the logic diagram for the directional overcurrent element
67-1.
Functions
2.3 Directional Overcurrent Protection 67, 67N
SIPROTEC 4, 7SJ62/64, Manual
89
C53000-G1140-C207-8, Edition 08.2016
Содержание SIPROTEC 4
Страница 8: ...8 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Страница 18: ...18 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Страница 30: ...30 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Страница 540: ...540 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Страница 594: ...594 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Страница 720: ...720 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...