Connection for flush-mounted
casing
Rear panel, mounting location “C”
Connection for surface-mounted
casing
at the housing mounted case on the case bottom
Optical Wavelength
λ = 820 nm
Laser Class 1 according to EN
60825-1/-2
using glass fiber 50/125 μm or using glass fiber 62.5/125 μm
Permissible Optical Link Signal
Attenuation
max. 8 dB, with glass fiber 62.5/125 μm
Maximum Distance of Transmission max. 0.93 miles (1.5 km)
Character Idle State
Configurable: factory setting “Light off”
1)
not for 7SJ64
Additional Interface (only 7SJ64)
Connection
isolated interface for data transfer with an RTD-box
Transmission Speed
min. 4,800 Baud; max. 115,200 Baud; Factory setting 38,400 Baud
RS485
Connection for flush-mounted
casing
rear panel, mounting location “D”,
9-pole D-SUB miniature female connector
Connection for surface-mounted
casing
at the housing bottom; shielded data cable
Test Voltage (PELV)
500 VAC; 50 Hz
Maximum Distance of Transmission 3,280 feet (1,000 m)
Fiber Optical Link (FO)
FO connector type
ST connector
Connection for flush-mounted
casing
Rear panel, mounting location “D”
Connection for surface-mounted
casing
at the housing mounted case on the case bottom
Optical Wavelength
λ = 820 nm
Laser Class 1 according to EN
60825-1/-2
using glass fiber 50/125 μm or using glass fiber 62.5/125 μm
Permissible Optical Link Signal
Attenuation
max. 8 dB, with glass fiber 62.5/125 μm
Maximum Distance of Transmission max. 0.93 miles (1.5 km)
Character Idle State
Configurable: factory setting “Light off”
System Interface
IEC 60870-5-103 single
RS232/RS485/FO according to the
ordering variant
isolated interface for data transfer to a master terminal
RS232
Connection for flush-mounted
casing
rear panel, mounting location “B”,
9-pole D-SUB miniature female connector
Connection for surface-mounted
casing
at the housing mounted case on the case bottom
Technical Data
4.1 General Device Data
442
SIPROTEC 4, 7SJ62/64, Manual
C53000-G1140-C207-8, Edition 08.2016
Содержание SIPROTEC 4
Страница 8: ...8 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Страница 18: ...18 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Страница 30: ...30 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Страница 540: ...540 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Страница 594: ...594 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Страница 720: ...720 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...