Trip Circuit Supervision
Please note that two binary inputs or one binary input and one bypass resistor R must be connected in series.
The pick-up threshold of the binary inputs must therefore be substantially below half the rated control DC
voltage.
If two binary inputs are used for the trip circuit supervision, these binary inputs must be isolated, i.o.w. not be
communed with each other or with another binary input.
If one binary input is used, a bypass resistor R must be inserted (see following figure). The resistor R is
connected in series with the second circuit breaker auxiliary contact (Aux2) to allow the detection of a trip
circuit failure even when circuit breaker auxiliary contact (Aux1) is open and the command relay has dropped
out. The value of this resistor must be such that in the circuit breaker open condition (Aux1 is open and Aux2
is closed) the circuit breaker trip coil (TC) is no longer picked up and binary input (BI1) is still picked up if the
command relay contact is open.
[prinzip-ausloesekrueb-1-be-wlk-010802, 1, en_GB]
Figure 3-2
Principle of the trip circuit supervision with one binary input
TR
Trip relay contact
CB
Circuit breaker
TC
Circuit breaker trip coil
Aux1
Circuit breaker auxiliary contact (NO contact)
Aux2
Circuit breaker auxiliary contact (NC contact)
U-CTR
Control voltage for trip circuit
U-BI
Input voltage of binary input
R
Bypass resistor
UR
Voltage across the bypass resistor
This results in an upper limit for the resistance dimension, R
max
and a lower limit R
min
, from which the optimal
value of the arithmetic mean R should be selected:
[formel-mittelwert-r-260602-kn, 1, en_GB]
In order that the minimum voltage for controlling the binary input is ensured, R
max
is derived as::
[formel-rmax-260602-kn, 1, en_GB]
Mounting and Commissioning
3.1 Mounting and Connections
180
SIPROTEC 4, 7VK61, Manual
C53000-G1176-C159-5, Edition 05.2018
Содержание SIPROTEC 4 7VK61
Страница 8: ...8 SIPROTEC 4 7VK61 Manual C53000 G1176 C159 5 Edition 05 2018 ...
Страница 10: ...10 SIPROTEC 4 7VK61 Manual C53000 G1176 C159 5 Edition 05 2018 ...
Страница 16: ...16 SIPROTEC 4 7VK61 Manual C53000 G1176 C159 5 Edition 05 2018 ...
Страница 176: ...176 SIPROTEC 4 7VK61 Manual C53000 G1176 C159 5 Edition 05 2018 ...
Страница 224: ...224 SIPROTEC 4 7VK61 Manual C53000 G1176 C159 5 Edition 05 2018 ...
Страница 264: ...264 SIPROTEC 4 7VK61 Manual C53000 G1176 C159 5 Edition 05 2018 ...
Страница 270: ...270 SIPROTEC 4 7VK61 Manual C53000 G1176 C159 5 Edition 05 2018 ...
Страница 276: ...276 SIPROTEC 4 7VK61 Manual C53000 G1176 C159 5 Edition 05 2018 ...
Страница 346: ...346 SIPROTEC 4 7VK61 Manual C53000 G1176 C159 5 Edition 05 2018 ...