Mounting and Connections
General
!
WARNING
Warning of improper transport, storage, installation, and application of the device.
Non-observance can result in death, personal injury or substantial property damage.
²
Trouble free and safe use of this device depends on proper transport, storage, installation, and appli-
cation of the device according to the warnings in this instruction manual.
²
Of particular importance are the general installation and safety regulations for work in a high-voltage
environment (for example, VDE, IEC, EN, DIN, or other national and international regulations). These
regulations must be observed.
Configuration Information
Prerequisites
For installation and connections the following conditions must be met:
The rated device data has been tested as recommended in the SIPROTEC 4 System Description and their
compliance with the Power System Data is verified.
Connection Variants
General Diagrams are shown in Appendix
. Connection examples for current trans-
former and voltage transformer circuits are provided in Appendix
that the setting of the
P.System Data 1
, Section
, was made in accordance to the
device connections.
Currents
shows current transformer connection examples in dependence on network
conditions.
For normal connection, address 220
I4 transformer
=
In prot. line
must be set and furthermore,
address 221
I4/Iph CT
=
1.000
.
When using separate earth current transformers, address 220
I4 transformer
=
In prot. line
must be
set. The setting value of the address 221
I4/Iph CT
may deviate from
1
. For information on the calculation,
Please observe that 2 CT-connection is permitted only for isolated or compensated networks.
Voltages
Connection examples for current and voltage transformer circuits are provided in Appendix
For the normal connection the 4th voltage measuring input is not used; correspondingly the address must be
set to 210
U4 transformer
=
Not connected
.
For an additional connection of an e-n-winding of a set of voltage transformers, the address 210
U4 trans-
former
=
Udelta transf.
must be set. The setting value of the address
Uph / Udelta
depends on the
transformation ratio of the e–n-winding. For additional hints, please refer to Section
under “Transformation Ratio”.
In further connection examples also the e–n winding of a set of voltage transformers is connected, in this
case, however of a central set of transformers at a busbar. For more information refer to the previous para-
graph.
3.1
3.1.1
Mounting and Commissioning
3.1 Mounting and Connections
178
SIPROTEC 4, 7VK61, Manual
C53000-G1176-C159-5, Edition 05.2018
Содержание SIPROTEC 4 7VK61
Страница 8: ...8 SIPROTEC 4 7VK61 Manual C53000 G1176 C159 5 Edition 05 2018 ...
Страница 10: ...10 SIPROTEC 4 7VK61 Manual C53000 G1176 C159 5 Edition 05 2018 ...
Страница 16: ...16 SIPROTEC 4 7VK61 Manual C53000 G1176 C159 5 Edition 05 2018 ...
Страница 176: ...176 SIPROTEC 4 7VK61 Manual C53000 G1176 C159 5 Edition 05 2018 ...
Страница 224: ...224 SIPROTEC 4 7VK61 Manual C53000 G1176 C159 5 Edition 05 2018 ...
Страница 264: ...264 SIPROTEC 4 7VK61 Manual C53000 G1176 C159 5 Edition 05 2018 ...
Страница 270: ...270 SIPROTEC 4 7VK61 Manual C53000 G1176 C159 5 Edition 05 2018 ...
Страница 276: ...276 SIPROTEC 4 7VK61 Manual C53000 G1176 C159 5 Edition 05 2018 ...
Страница 346: ...346 SIPROTEC 4 7VK61 Manual C53000 G1176 C159 5 Edition 05 2018 ...