![Siemens SIPROTEC 4 7VK61 Скачать руководство пользователя страница 248](http://html.mh-extra.com/html/siemens/siprotec-4-7vk61/siprotec-4-7vk61_manual_382659248.webp)
Monitoring Functions
Measured values
Current sum
Ι
F
= |
Ι
L1
+
Ι
L2
+
Ι
L3
+ k
Ι
·
Ι
E
| >
SUM.I Threshold ·
Ι
N
+ SUM.FACTOR
Ι
·Σ |
Ι
|
- SUM.
Ι
Limit
for
Ι
N
= 1 A
0.05 A to 2.00 A
Increments 0.01 A
for
Ι
N
= 5 A
0.25 A to 10.00 A
Increments 0.01 A
- SUM.FACTOR
Ι
0.00 to 0.95
Increments 0.01
Voltage sum
U
F
= | U
L1
+ U
L2
+ U
L3
+ k
U
· U
EN
| > 25 V
Current Symmetry
|
Ι
min
|/|
Ι
max
| < BAL.FACTOR.
Ι
as long as
Ι
max
/
Ι
N
> BAL.
Ι
LIMIT/
Ι
N
- BAL.FACTOR.
Ι
0.10 to 0.95
Increments 0.01
BAL.
Ι
LIMIT
for
Ι
N
= 1 A
0.10 A to 1.00 A
Increments 0.01 A
for
Ι
N
= 5 A
0.50 A to 5.00 A
Increments 0.01 A
T BAL.
Ι
LIMIT
5 s to 100 s
Increments 1 s
Broken conductor
One conductor without current, the others with current
(monitoring of current transformer circuits on current step
change in one phase without residual current)
Voltage Symmetry
| U
min
|/| U
max
| < BAL.FACTOR.U
as long as | U
max
| > BAL.ULIMIT
- BAL.FACTORU
0.58 to 0.95
Increments 0.01
- BAL.ULIMIT
10 V to 100 V
Increments 1 V
- T BAL.ULIMIT
5 s to 100 s
Increments 1 s
Voltage phase sequence
U
L1
before U
L2
before U
L3
as long as | U
L1
|. | U
L2
| . | U
L3
| > 40 V/√3
Non-symmetrical voltages
(Fuse failure monitoring)
3 · U
0
> FFM U> or 3 · U
2
> FFM U>
and at the same time
3 ·
Ι
0
< FFM
Ι
< and 3 ·
Ι
2
< FFM
Ι
<
- FFM U>
10 V to 100 V
Increments 1 V
- FFM
Ι
<
for
Ι
N
= 1 A
0.10 A to 1.00 A
Increments 0.01 A
for
Ι
N
= 5 A
0.50 A to 5.00 A
Increments 0.01 A
Three-phase measuring voltage failure
(Fuse failure monitoring)
all U
Ph-E
< FFM UMEAS <
and at the same time
all Δ
Ι
Ph
< FFM
Ι
delta
and
all
Ι
Ph
> (
Ι
Ph
> (Dist.))
- FFM UMEAS <
2 V to 100 V
Increments 1 V
- FFM
Ι
delta
for
Ι
N
= 1 A
0.05 A to 1.00 A
Increments 0.01 A
for
Ι
N
= 5 A
0.25 A to 5.00 A
Increments 0.01 A
- T U SUPERVISION (wait time for additional measured
voltage failure monitoring)
0.00 s to 30.00 s
Increments 0.01 s
- T U mcb
0 ms to 30 ms
Increments 1 ms
Phase angle positive sequence power
Message when the angle lies inside the area of the P-Q level
parameterised by φA and φB
- φA, φB
0° to 259°
Increments 1°
4.7
Technical Data
4.7 Monitoring Functions
248
SIPROTEC 4, 7VK61, Manual
C53000-G1176-C159-5, Edition 05.2018
Содержание SIPROTEC 4 7VK61
Страница 8: ...8 SIPROTEC 4 7VK61 Manual C53000 G1176 C159 5 Edition 05 2018 ...
Страница 10: ...10 SIPROTEC 4 7VK61 Manual C53000 G1176 C159 5 Edition 05 2018 ...
Страница 16: ...16 SIPROTEC 4 7VK61 Manual C53000 G1176 C159 5 Edition 05 2018 ...
Страница 176: ...176 SIPROTEC 4 7VK61 Manual C53000 G1176 C159 5 Edition 05 2018 ...
Страница 224: ...224 SIPROTEC 4 7VK61 Manual C53000 G1176 C159 5 Edition 05 2018 ...
Страница 264: ...264 SIPROTEC 4 7VK61 Manual C53000 G1176 C159 5 Edition 05 2018 ...
Страница 270: ...270 SIPROTEC 4 7VK61 Manual C53000 G1176 C159 5 Edition 05 2018 ...
Страница 276: ...276 SIPROTEC 4 7VK61 Manual C53000 G1176 C159 5 Edition 05 2018 ...
Страница 346: ...346 SIPROTEC 4 7VK61 Manual C53000 G1176 C159 5 Edition 05 2018 ...