Addr. Parameter
Function
C
Setting Options
Default Setting
Comments
3721 3U0>(>) (or Ux)
Voltage Prot.
OFF
Alarm Only
ON
U>Alarm U>>Trip
OFF
Operating mode 3U0 (or
Ux) overvoltage
3722 3U0>
Voltage Prot.
1.0 .. 220.0 V
30.0 V
3U0>: Pickup value (or
Ux>)
3723 T 3U0>
Voltage Prot.
0.00 .. 100.00 sec
2.00 sec
3U0>: Time delay (or
Ux>)
3724 3U0>>
Voltage Prot.
1.0 .. 220.0 V
50.0 V
3U0>>: Pickup value (or
Ux>>)
3725 T 3U0>>
Voltage Prot.
0.00 .. 100.00 sec
1.00 sec
3U0>>: Time delay (or
Ux>>)
3728A 3U0>(>) Stabil.
Voltage Prot.
ON
OFF
ON
3U0>(>): Stabilization
3U0-Measurement
3729A 3U0>(>) RESET
Voltage Prot.
0.30 .. 0.99
0.95
3U0>(>): Resetting ratio
(or Ux)
3731 U1>(>)
Voltage Prot.
OFF
Alarm Only
ON
U>Alarm U>>Trip
OFF
Operating mode U1 over-
voltage prot.
3732 U1>
Voltage Prot.
2.0 .. 220.0 V
150.0 V
V1>: 5A
3733 T U1>
Voltage Prot.
0.00 .. 100.00 sec
2.00 sec
V1>: Time delay
3734 U1>>
Voltage Prot.
2.0 .. 220.0 V
175.0 V
V1>>: 5A
3735 T U1>>
Voltage Prot.
0.00 .. 100.00 sec
1.00 sec
V1>>: Time delay
3739A U1>(>) RESET
Voltage Prot.
0.30 .. 0.99
0.98
V1>(>): Dropout to
pickup ratio
3741 U2>(>)
Voltage Prot.
OFF
Alarm Only
ON
U>Alarm U>>Trip
OFF
Operating mode U2 over-
voltage prot.
3742 U2>
Voltage Prot.
2.0 .. 220.0 V
30.0 V
V2> 5A
3743 T U2>
Voltage Prot.
0.00 .. 100.00 sec
2.00 sec
V2> Time delay
3744 U2>>
Voltage Prot.
2.0 .. 220.0 V
50.0 V
V2>>: 5A
3745 T U2>>
Voltage Prot.
0.00 .. 100.00 sec
1.00 sec
V2>>: Time delay
3749A U2>(>) RESET
Voltage Prot.
0.30 .. 0.99
0.98
V2>(>): Dropout to
pickup ratio
3751 Uph-e<(<)
Voltage Prot.
OFF
Alarm Only
ON
U<Alarm U<<Trip
OFF
Operating mode Ph-E
undervoltage prot.
3752 Uph-e<
Voltage Prot.
1.0 .. 100.0 V
30.0 V
Uph<: 5A
3753 T Uph-e<
Voltage Prot.
0.00 .. 100.00 sec
2.00 sec
Uph<: Time delay
3754 Uph-e<<
Voltage Prot.
1.0 .. 100.0 V
10.0 V
Uph<<: 5A
3755 T Uph-e<<
Voltage Prot.
0.00 .. 100.00 sec
1.00 sec
Uph<<: Time delay
3758 CURR.SUP. Uphe<
Voltage Prot.
ON
OFF
ON
Uph<(<): Current criterion
3759A Uph-e<(<) RESET
Voltage Prot.
1.01 .. 1.20
1.05
Uph<(<): Dropout to
pickup ratio
Functions, Settings, Information
E.2 Settings
SIPROTEC 4, 7VK61, Manual
305
C53000-G1176-C159-5, Edition 05.2018
Содержание SIPROTEC 4 7VK61
Страница 8: ...8 SIPROTEC 4 7VK61 Manual C53000 G1176 C159 5 Edition 05 2018 ...
Страница 10: ...10 SIPROTEC 4 7VK61 Manual C53000 G1176 C159 5 Edition 05 2018 ...
Страница 16: ...16 SIPROTEC 4 7VK61 Manual C53000 G1176 C159 5 Edition 05 2018 ...
Страница 176: ...176 SIPROTEC 4 7VK61 Manual C53000 G1176 C159 5 Edition 05 2018 ...
Страница 224: ...224 SIPROTEC 4 7VK61 Manual C53000 G1176 C159 5 Edition 05 2018 ...
Страница 264: ...264 SIPROTEC 4 7VK61 Manual C53000 G1176 C159 5 Edition 05 2018 ...
Страница 270: ...270 SIPROTEC 4 7VK61 Manual C53000 G1176 C159 5 Edition 05 2018 ...
Страница 276: ...276 SIPROTEC 4 7VK61 Manual C53000 G1176 C159 5 Edition 05 2018 ...
Страница 346: ...346 SIPROTEC 4 7VK61 Manual C53000 G1176 C159 5 Edition 05 2018 ...