The trip circuit supervision does not operate during system faults. A momentary closed tripping contact does
not lead to a fault indication. If, however, other trip relay contacts from different devices are connected in
parallel in the trip circuit, the fault indication must be delayed by
Alarm Delay
(see also
). After
clearance of the failure in the trip circuit, the fault message automatically resets with the same time delay.
[logikdiagramm-auskruebrwchg-1-be-wlk-310702, 1, en_GB]
Figure 2-62
Logic diagram for trip circuit supervision with one binary input
Setting Notes
General
The number of circuits to be supervised was set during the configuration in address 140
Trip Cir. Sup.
). If the trip circuit supervision is not used at all, the setting
Disabled
must be
applied there.
The trip circuit supervision can be switched in address 4001
FCT TripSuperv.
ON
- or
OFF
. The number of
binary inputs that shall be used in each of the supervised circuits is set in address 4002
No. of BI
. If the
routing of the required binary inputs does not comply with the selected monitoring mode, an alarm is issued
(
TripC ProgFAIL...
with identification of the non-compliant circuit).
Supervision with one binary input
The alarm for supervision with two binary inputs is always delayed by approx. 1s to 2s, whereas the delay time
of the alarm for supervision with one binary input can be set in address 4003
Alarm Delay
. If only the
device 7VK61 is connected to the trip circuits 1 s to 2 s are sufficient, as the trip circuit supervision does not
operate during a system fault. If, however, trip contacts from other devices are connected in parallel in the trip
circuit, the alarm must be delayed such that the longest trip command duration can be reliably bridged.
Settings
Addr.
Parameter
Setting Options
Default Setting
Comments
4001
FCT TripSuperv.
ON
OFF
OFF
TRIP Circuit Supervision is
4002
No. of BI
1 .. 2
2
Number of Binary Inputs per trip
circuit
4003
Alarm Delay
1 .. 30 sec
2 sec
Delay Time for alarm
Information List
No.
Information
Type of
Informa-
tion
Comments
6854
>TripC1 TripRel
SP
>Trip circuit superv. 1: Trip Relay
6855
>TripC1 Bkr.Rel
SP
>Trip circuit superv. 1: Breaker Relay
6856
>TripC2 TripRel
SP
>Trip circuit superv. 2: Trip Relay
6857
>TripC2 Bkr.Rel
SP
>Trip circuit superv. 2: Breaker Relay
6858
>TripC3 TripRel
SP
>Trip circuit superv. 3: Trip Relay
6859
>TripC3 Bkr.Rel
SP
>Trip circuit superv. 3: Breaker Relay
6861
TripC OFF
OUT
Trip circuit supervision OFF
6865
FAIL: Trip cir.
OUT
Failure Trip Circuit
6866
TripC1 ProgFAIL
OUT
TripC1 blocked: Binary input is not set
2.7.2.2
2.7.2.3
2.7.2.4
Functions
2.7 Monitoring Functions
SIPROTEC 4, 7VK61, Manual
147
C53000-G1176-C159-5, Edition 05.2018
Содержание SIPROTEC 4 7VK61
Страница 8: ...8 SIPROTEC 4 7VK61 Manual C53000 G1176 C159 5 Edition 05 2018 ...
Страница 10: ...10 SIPROTEC 4 7VK61 Manual C53000 G1176 C159 5 Edition 05 2018 ...
Страница 16: ...16 SIPROTEC 4 7VK61 Manual C53000 G1176 C159 5 Edition 05 2018 ...
Страница 176: ...176 SIPROTEC 4 7VK61 Manual C53000 G1176 C159 5 Edition 05 2018 ...
Страница 224: ...224 SIPROTEC 4 7VK61 Manual C53000 G1176 C159 5 Edition 05 2018 ...
Страница 264: ...264 SIPROTEC 4 7VK61 Manual C53000 G1176 C159 5 Edition 05 2018 ...
Страница 270: ...270 SIPROTEC 4 7VK61 Manual C53000 G1176 C159 5 Edition 05 2018 ...
Страница 276: ...276 SIPROTEC 4 7VK61 Manual C53000 G1176 C159 5 Edition 05 2018 ...
Страница 346: ...346 SIPROTEC 4 7VK61 Manual C53000 G1176 C159 5 Edition 05 2018 ...