Addr.
Parameter
Function
Setting Options
Default Setting
Comments
6126
Unom SECONDARY SYNC function 1 80 .. 125 V
100 V
Rated Secondary Voltage
(Ph-Ph)
6127
T CLS CMD MIN
SYNC function 1 0.01 .. 10.00 sec
0.10 sec
Min close command time of
the CB
6130
dU ASYN U2>U1
SYNC function 1 0.0 .. 40.0 V
2.0 V
Maximum voltage differ-
ence U2>U1
6131
dU ASYN U2<U1
SYNC function 1 0.0 .. 40.0 V
2.0 V
Maximum voltage differ-
ence U2<U1
6132
df ASYN f2>f1
SYNC function 1 0.00 .. 2.00 Hz
0.10 Hz
Maximum frequency differ-
ence f2>f1
6133
df ASYN f2<f1
SYNC function 1 0.00 .. 2.00 Hz
0.10 Hz
Maximum frequency differ-
ence f2<f1
6140
SYNC PERMIS.
SYNC function 1 NO
YES
NO
Switching at synchronous
conditions
6141
F SYNCHRON
SYNC function 1 0.01 .. 0.04 Hz
0.01 Hz
Frequency threshold ASYN
<--> SYN
6142
dU SYN U2>U1
SYNC function 1 0.0 .. 40.0 V
2.0 V
Maximum voltage differ-
ence U2>U1
6143
dU SYN U2<U1
SYNC function 1 0.0 .. 40.0 V
2.0 V
Maximum voltage differ-
ence U2<U1
6144
dα SYN α2>α1
SYNC function 1 2 .. 80 °
10 °
Maximum angle difference
alpha2>alpha1
6145
dα SYN α2<α1
SYNC function 1 2 .. 80 °
10 °
Maximum angle difference
alpha2<alpha1
6146
T SYNC-DELAY
SYNC function 1 0.00 .. 60.00 sec
10.00 sec
Release delay at synchro-
nous conditions
6150
dU SYNC U2>U1
SYNC function 1 0.0 .. 40.0 V
2.0 V
Maximum voltage differ-
ence U2>U1
6151
dU SYNC U2<U1
SYNC function 1 0.0 .. 40.0 V
2.0 V
Maximum voltage differ-
ence U2<U1
6152
df SYNC f2>f1
SYNC function 1 0.00 .. 2.00 Hz
0.10 Hz
Maximum frequency differ-
ence f2>f1
6153
df SYNC f2<f1
SYNC function 1 0.00 .. 2.00 Hz
0.10 Hz
Maximum frequency differ-
ence f2<f1
6154
dα SYNC α2> α1
SYNC function 1 2 .. 80 °
10 °
Maximum angle difference
alpha2>alpha1
6155
dα SYNC α2< α1
SYNC function 1 2 .. 80 °
10 °
Maximum angle difference
alpha2<alpha1
6160
TAP CHG. OBJ.
SYNC function 1 OBJVERWparaMEIN-
STELL
none
Tap changer object
6161
#STEP NOM. VOLT
SYNC function 1 -62 .. 62
0
# of tap changer at nom.
voltage
6162
TAP STEP
SYNC function 1 -20.00 .. 20.00 %
0.00 %
Step size tap changer
6170
U BALANCING
SYNC function 1 OFF
Tap changer
Pulse
OFF
Voltage balancing
6171
T U PULS MIN
SYNC function 1 10 .. 1000 ms
100 ms
Minimum pulse duration for
U balancing
6172
T U PULS MAX
SYNC function 1 1.00 .. 32.00 sec
1.00 sec
Maximum pulse duration
for U balancing
6173
dU2 / dt
SYNC function 1 0.1 .. 50.0 V/s
2.0 V/s
dU/dt of the controller
Functions, Settings, Information
E.2 Settings
264
SIPROTEC 4, 7VE61 and 7VE63, Manual
C53000-G1176-C163-3, Edition 10.2017
Содержание SIPROTEC 4 7VE61
Страница 8: ...8 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Страница 24: ...24 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Страница 142: ...142 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Страница 192: ...192 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Страница 222: ...222 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Страница 230: ...230 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Страница 256: ...256 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Страница 314: ...314 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Страница 316: ...316 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Страница 330: ...330 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...