Task Level
Limit in TICKS
1)
SFS_BEARB (Interlocking)
10000
1)
When the sum of TICKS of all blocks exceeds the limits before-mentioned, an error message is output by CFC.
Processing times in TICKS required by the individual elements
Individual Element
Number of TICKS
Module, basic requirement
5
Each input from the 3rd additional input for generic blocks
1
Connection to an input signal
6
Connection to an output signal
7
Additional for each chart
1
Arithmetic
ABS_VALUE
5
ADD
26
SUB
26
MUL
26
DIV
54
SQUARE_ROOT
83
Basis logic
AND
5
CONNECT
4
DYN_OR
6
NAND
5
NEG
4
NOR
5
OR
5
RISE_DETECT
4
X_OR
5
Information status
SI_GET_STATUS
5
CV_GET_STATUS
5
DI_GET_STATUS
5
MV_GET_STATUS
5
SI_SET_STATUS
5
DI_SET_STATUS
5
MV_SET_STATUS
5
ST_AND
5
ST_OR
5
ST_NOT
5
Memory
D_FF
5
D_FF_MEMO
6
RS_FF
4
RS_FF_MEMO
4
SR_FF
4
SR_FF_MEMO
4
Control commands
BOOL_TO_CO
5
BOOL_TO_IC
5
CMD_INF
4
CMD_INF_EXE
4
CMD_CHAIN
34
CMD_CANCEL
3
Technical Data
4.11 User-defined functions (CFC)
SIPROTEC 4, 7VE61 and 7VE63, Manual
215
C53000-G1176-C163-3, Edition 10.2017
Содержание SIPROTEC 4 7VE61
Страница 8: ...8 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Страница 24: ...24 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Страница 142: ...142 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Страница 192: ...192 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Страница 222: ...222 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Страница 230: ...230 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Страница 256: ...256 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Страница 314: ...314 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Страница 316: ...316 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...