Monitoring
possible causes
Malfunction Response Indication (No.)
Output
Relay monitoring
Internal (hardware
Indication
Error Relay R1
(25041)
Error Relay R2
(25042)
Synchronizing is
blocked
Plausibility monitorings Configuration errors
Parametrization errors
Indication
Sync Fail.Conf.
(222.2331)
Sy1 ParErr
(170.2097)
Synchronizing is
blocked
Offset monitoring
Internal (hardware)
Indication
Error Offset
(191)
Synchronizing is
blocked
1)
After three unsuccessful restarts, the device is taken out of service.
2)
DOK = "Device Okay" = Ready for service relay drops off, synchronizing protection and control functions are
blocked. Operator communication is still possible
Group indications
Certain indications of the monitoring functions are combined as group indications. These group indications
(disturbance group indication 140, warning group indication 160 and disturbance measured value 181) and
their composition are described in the Appendix
.
Information List
No.
Information
Type of
Informa-
tion
Comments
68
Clock SyncError
OUT
Clock Synchronization Error
140
Error Sum Alarm
OUT
Error with a summary alarm
160
Alarm Sum Event
OUT
Alarm Summary Event
170.2097 Sy1 ParErr
OUT
Sync-group 1: Parameter not plausible
170.2097 Sy2 ParErr
OUT
Sync-group 2: Parameter not plausible
170.2097 Sy3 ParErr
OUT
Sync-group 3: Parameter not plausible
170.2097 Sy4 ParErr
OUT
Sync-group 4: Parameter not plausible
170.2097 Sy5 ParErr
OUT
Sync-group 5: Parameter not plausible
170.2097 Sy6 ParErr
OUT
Sync-group 6: Parameter not plausible
170.2097 Sy7 ParErr
OUT
Sync-group 7: Parameter not plausible
170.2097 Sy8 ParErr
OUT
Sync-group 8: Parameter not plausible
177
Fail Battery
OUT
Failure: Battery empty
181
Error A/D-conv.
OUT
Error: A/D converter
183
Error Board 1
OUT
Error Board 1
184
Error Board 2
OUT
Error Board 2
185
Error Board 3
OUT
Error Board 3
186
Error Board 4
OUT
Error Board 4
187
Error Board 5
OUT
Error Board 5
188
Error Board 6
OUT
Error Board 6
189
Error Board 7
OUT
Error Board 7
190
Error Board 0
OUT
Error Board 0
191
Error Offset
OUT
Error: Offset
193
Alarm adjustm.
OUT
Alarm: Analog input adjustment invalid
2.12.5
Functions
2.12 Supervision
116
SIPROTEC 4, 7VE61 and 7VE63, Manual
C53000-G1176-C163-3, Edition 10.2017
Содержание SIPROTEC 4 7VE61
Страница 8: ...8 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Страница 24: ...24 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Страница 142: ...142 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Страница 192: ...192 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Страница 222: ...222 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Страница 230: ...230 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Страница 256: ...256 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Страница 314: ...314 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Страница 316: ...316 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Страница 330: ...330 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...