Addr.
Parameter
Function
Setting Options
Default Setting
Comments
6630
dU ASYN U2>U1
SYNC function 6 0.0 .. 40.0 V
2.0 V
Maximum voltage differ-
ence U2>U1
6631
dU ASYN U2<U1
SYNC function 6 0.0 .. 40.0 V
2.0 V
Maximum voltage differ-
ence U2<U1
6632
df ASYN f2>f1
SYNC function 6 0.00 .. 2.00 Hz
0.10 Hz
Maximum frequency differ-
ence f2>f1
6633
df ASYN f2<f1
SYNC function 6 0.00 .. 2.00 Hz
0.10 Hz
Maximum frequency differ-
ence f2<f1
6640
SYNC PERMIS.
SYNC function 6 NO
YES
NO
Switching at synchronous
conditions
6641
F SYNCHRON
SYNC function 6 0.01 .. 0.04 Hz
0.01 Hz
Frequency threshold ASYN
<--> SYN
6642
dU SYN U2>U1
SYNC function 6 0.0 .. 40.0 V
2.0 V
Maximum voltage differ-
ence U2>U1
6643
dU SYN U2<U1
SYNC function 6 0.0 .. 40.0 V
2.0 V
Maximum voltage differ-
ence U2<U1
6644
dα SYN α2>α1
SYNC function 6 2 .. 80 °
10 °
Maximum angle difference
alpha2>alpha1
6645
dα SYN α2<α1
SYNC function 6 2 .. 80 °
10 °
Maximum angle difference
alpha2<alpha1
6646
T SYNC-DELAY
SYNC function 6 0.00 .. 60.00 sec
10.00 sec
Release delay at synchro-
nous conditions
6650
dU SYNC U2>U1
SYNC function 6 0.0 .. 40.0 V
2.0 V
Maximum voltage differ-
ence U2>U1
6651
dU SYNC U2<U1
SYNC function 6 0.0 .. 40.0 V
2.0 V
Maximum voltage differ-
ence U2<U1
6652
df SYNC f2>f1
SYNC function 6 0.00 .. 2.00 Hz
0.10 Hz
Maximum frequency differ-
ence f2>f1
6653
df SYNC f2<f1
SYNC function 6 0.00 .. 2.00 Hz
0.10 Hz
Maximum frequency differ-
ence f2<f1
6654
dα SYNC α2> α1
SYNC function 6 2 .. 80 °
10 °
Maximum angle difference
alpha2>alpha1
6655
dα SYNC α2< α1
SYNC function 6 2 .. 80 °
10 °
Maximum angle difference
alpha2<alpha1
6660
TAP CHG. OBJ.
SYNC function 6 OBJVERWparaMEIN-
STELL
none
Tap changer object
6661
#STEP NOM. VOLT
SYNC function 6 -62 .. 62
0
# of tap changer at nom.
voltage
6662
TAP STEP
SYNC function 6 -20.00 .. 20.00 %
0.00 %
Step size tap changer
6670
U BALANCING
SYNC function 6 OFF
Tap changer
Pulse
OFF
Voltage balancing
6671
T U PULS MIN
SYNC function 6 10 .. 1000 ms
100 ms
Minimum pulse duration for
U balancing
6672
T U PULS MAX
SYNC function 6 1.00 .. 32.00 sec
1.00 sec
Maximum pulse duration
for U balancing
6673
dU2 / dt
SYNC function 6 0.1 .. 50.0 V/s
2.0 V/s
dU/dt of the controller
6674
T U PAUSE
SYNC function 6 0.00 .. 32.00 sec
5.00 sec
Transient time of the U-
controller
6675A SMOOTHING U
SYNC function 6 1 .. 100
1
Smoothing factor for the
voltage
Functions, Settings, Information
E.2 Settings
SIPROTEC 4, 7VE61 and 7VE63, Manual
275
C53000-G1176-C163-3, Edition 10.2017
Содержание SIPROTEC 4 7VE61
Страница 8: ...8 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Страница 24: ...24 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Страница 142: ...142 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Страница 192: ...192 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Страница 222: ...222 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Страница 230: ...230 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Страница 256: ...256 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Страница 314: ...314 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Страница 316: ...316 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Страница 330: ...330 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...